INSP-Final Inspection | 12/28/2007 | 12/31/2007 | 12/31/2007 | A | PASS |
Troy Cobbley
|
|
|
Complete final inspection, all corections were made per last inspections. KR
|
INSP-Supply line flush | 12/28/2007 | 12/31/2007 | 12/31/2007 | A | PASS |
Troy Cobbley
|
|
|
Complete supply line flush.KR
|
INSP-Final Inspection | 12/28/2007 | 12/28/2007 | 12/28/2007 | P | FAIL |
Troy Cobbley
|
|
|
All corrections were made per Troys notes.The supplie line flush was not completed during this inspection,They will call it in for next week.KR
|
INSP-Final Inspection | 10/3/2007 | 10/3/2007 | 10/4/2007 | P | FAIL |
Troy Cobbley
|
|
|
Provide orfice in the sprinkler test line and test the flow switch and alarm bell. Flush the underground supply piping. Provide signage at the riser. Provide hydraulic sticker, head box, spare sprinklers and head wrench. Mount the riser against the wall. Provide the missing sprinkler canopies and replace the sprinkler canopies that have been painted unless verification can be provided that they were factory painted.
|
INSP-Final Inspection | 4/13/2007 | 4/16/2007 | 4/16/2007 | A | FAIL |
Troy Cobbley
|
|
|
Relocate pendant that is too close to wall on the second floor and provide approved plans on site. Remove handles from the valves.
|
INSP-Sprinkler Rough-in | 5/17/2006 | 5/18/2006 | 5/18/2006 | A | PASS |
Troy Cobbley
|
|
|
Sprinkler piping in dining area is ok for cover
|
INSP-Sprinkler Rough-in | 5/5/2006 | 5/8/2006 | 5/8/2006 | P | PART |
Troy Cobbley
|
|
|
Sprinkler piping is ok to cover except for the dining room area due to the pendant being overspaced and not tented. Per Bill plans need to be resubmitted showing the six added pendants, the corrected underground supply and the correct backflow preventor.
|
INSP-Final Inspection | 5/5/2006 | 5/8/2006 | 5/5/2006 | P | CANC |
Troy Cobbley
|
|
|
James is the contact at ###-####. Thanks; Phone #: ###-#### Internet Inspection Request from: Trent Bice Inspection cancelled from web by: Trent Bice
|