Permit NumberFIR06-00223
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 3964 W QUAIL HILL CT
Project NameSPR CSC HOMES LLC
Customer Number 
ePlanReview 
Description
CSC HOMES LLC * To install a (modified) life safety NFPA 13D system in a five bedroom, three bathroom 4,057-ft/2 single family dwelling (2,326-ft/2 first floor, 1,731-ft/2 second floor), with an attached 888-ft/2 three car garage. The modification is the installation of a single row of dry sidewall sprinklers along the common wall attached to the garage and the living space. System shall be equipped with an alarm initiating device and an outside alarm. All fire sprinkler work and related, which includes dual use, single service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD05-01447.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/28/200712/31/200712/31/2007APASS
DetailsTroy Cobbley
Complete final inspection, all corections were made per last inspections. KR
INSP-Supply line flush12/28/200712/31/200712/31/2007APASS
DetailsTroy Cobbley
Complete supply line flush.KR
INSP-Final Inspection12/28/200712/28/200712/28/2007PFAIL
DetailsTroy Cobbley
All corrections were made per Troys notes.The supplie line flush was not completed during this inspection,They will call it in for next week.KR
INSP-Final Inspection10/3/200710/3/200710/4/2007PFAIL
DetailsTroy Cobbley
Provide orfice in the sprinkler test line and test the flow switch and alarm bell. Flush the underground supply piping. Provide signage at the riser. Provide hydraulic sticker, head box, spare sprinklers and head wrench. Mount the riser against the wall. Provide the missing sprinkler canopies and replace the sprinkler canopies that have been painted unless verification can be provided that they were factory painted.
INSP-Final Inspection4/13/20074/16/20074/16/2007AFAIL
DetailsTroy Cobbley
Relocate pendant that is too close to wall on the second floor and provide approved plans on site. Remove handles from the valves.
INSP-Sprinkler Rough-in5/17/20065/18/20065/18/2006APASS
DetailsTroy Cobbley
Sprinkler piping in dining area is ok for cover
INSP-Sprinkler Rough-in5/5/20065/8/20065/8/2006PPART
DetailsTroy Cobbley
Sprinkler piping is ok to cover except for the dining room area due to the pendant being overspaced and not tented. Per Bill plans need to be resubmitted showing the six added pendants, the corrected underground supply and the correct backflow preventor.
INSP-Final Inspection5/5/20065/8/20065/5/2006PCANC
DetailsTroy Cobbley
James is the contact at ###-####. Thanks; Phone #: ###-#### Internet Inspection Request from: Trent Bice Inspection cancelled from web by: Trent Bice