Permit NumberFIR06-00229
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1900 S COLE RD
Project NameSPR COMMERCIAL TIRE ADDITION
Customer Number 
ePlanReview 
Description
COMMERCIAL TIRE - BUILDING ADDITION * To install and extension of and an existing wet system into a new 3,520-ft/2, one story addition located on the east side of the existing 11,035-ft/2, one story Commercial Tire, retail and auto repair building. Fire sprinkler work is related to the riser being modified with the installation of a new wall P.I. attached to a new backflow preventer, system piping with ESFR protection in the attached new masonry exterior walls, concrete slab floor and metal roof building addition which will be used to for wheel alignment work and tire storage. Related building permit work (no sprinkler work identified) includes the remodel of the existing men's and women's restroom. This building will be fully fire sprinklered. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-02812.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/5/20065/5/20065/5/2006PPASS
DetailsTroy Cobbley
Fire sprinklers finaled
INSP-Sprinkler Rough-in/Hydro5/4/20065/4/20065/4/2006PPASS
DetailsTroy Cobbley
Permit is ok to final when the fire alarm permit is finaled.
INSP-Sprinkler Rough-in/Hydro5/3/20065/4/20065/4/2006ACANC
DetailsTroy Cobbley
jim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles reshedule for pm
INSP-Sprinkler Rough-in/Hydro5/3/20065/3/20065/3/2006PPASS
DetailsTroy Cobbley
Above ground hydro test passed. I performed a partial rough-in inspection. The EFSR heads were too close to the truss webbing. Some EQ bracing still needed to be installed.
INSP-Sprinkler Rough-in/Hydro5/3/20065/3/20065/3/2006PCANC
DetailsTroy Cobbley
jim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles wants to rescheduled for 5/4/2006