Permit Information
Permit NumberFIR06-00247
StatusFinaled
Name VANGUARD PROTECTION GROUP
Site Address 1666 S ENTERTAINMENT AVE
Project Namealm -FUDDRUCKERS RESTAURANT
Customer Number 
ePlanReview 
Description
To provide a required manual fire alarm system. The required manual fire alarm system includes sprinkler monitoring, HVAC shutdown, cooking hood monitoring and notification throughout.

The associated building permit (BLD 05-02489) is to construct a 7,841 sq. ft. one story Type VB fully fire sprinkled restaurant. Other work includes all site improvements, paving and landscaping per approved plans and attachments, DR05-0233. Fire sprinklers used for area. (Fuddruckers Restaurant)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/2/20066/5/20066/5/2006PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection5/31/20066/2/20066/2/2006PPART
DetailsTroy Cobbley
A temporary occupancy was given with Dave Hannimans permission until the correct covers are installed on the a/v's in the outdoor area. Life safety is ok to final when fire alarm is finaled.
INSP-Final Inspection5/26/20065/30/20065/30/2006AFAIL
DetailsTroy Cobbley
keith; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles

Items need to be addressed prior to inspection:

1) Resubmittal required
2) Pull station at SE exit at 51"
3) duct detectors are not installed per manufacturer's installation requirements. Inspector will accept differential reading (inspector verifies) or third party measurements.
4) Ceiling mounted H/S are overspaced (internal)
5) Exterior H/S have Gentex WP covers, cutsheet required at resubmittal to verify no visual loss.

Tested the following:

Water flow: address 11
Tampers (5): address 12
PIV (1): address 13
INSP-Final Inspection5/26/20065/26/20065/26/2006PFAIL
DetailsForrest France
HVAC units were not in a condition to allow testing of the duct smoke detectors (T-stats not installed), FACP currently in alarm due to ansul system testing, fire sprinkler riser devices not tested as sprinkler contractor has correction items to address, discussed some previously noted issues with alarm contractor including a/v spacing, back boxes, manual pulls, and as-builts. Due to conditions of the project no final inspection could be performed, requested contractor to reschedule when ready for final, also noted that EOL's have changed from approved plans.
INSP-Final Inspection5/25/20065/25/20065/25/2006PFAIL
DetailsTroy Cobbley
No real inspection was performed due to items found just walking around. Manual pull stations and the wall mounted a/v on the kitchen wall(facing dining) are mounted too high. Not all heights have been verified. Also the ceiling mounted a/v's are mounted above 10' which means reduced spacing is used. If, since spacing has not been checked yet, the a/v's are overspaced and the contractor wants to just increase the cd rating, resubmittals will be required. Mary was at this inspection as well and knows what is going on.