Permit Information
Permit NumberFIR06-00272
StatusFinaled
Name ALARMCO
Site Address 815 W ANN MORRISON PARK DR
Project Namealm - CHARLIE FROG SCHOOLS
Customer Number 
ePlanReview 
Description
To provide a required manual fire alarm system. The required manual fire alarm system includes sprinkler monitoring, HVAC shutdown (four units are indicated on the plans) and notification throughout.

The associated building permit (BLD 05-00426) is to remodel 10,134 sq.ft. Type VB, fully fire sprinklered one story existing building shell for preschool & unfinished future tenant space. Daycare space will have 6,997 sq. ft. with future space to have 3137 sq. ft. Daycare will have a manual fire alarm system as regulated by the Fire Dept. All work per approved plans and attachments and CUP03-00120 MOD #2 & DRH04-00013 MOD #2. Work includes all site improvements, paving and landscaping. Fire sprinklers used for area and installation is as regulated by the Fire Dept. No occupancy is authorized under this permit. The certificate of occupancy for the preschool occupancy is under permit MIS05-00108. The future tenant space will require separate plans and permits. The construction for the preschool is through finish under this permit. (CHARLIE FROG SCHOOLS-PRE SCHOOL & DAYCARE)

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/26/20067/27/20067/27/2006APASS
DetailsForrest France
Required corrections have been verified, one non functional RTS for duct detector 12 has been repaired, fire alarm permit finaled.
INSP-Final Inspection7/24/20067/25/20067/25/2006AFAIL
DetailsForrest France
Descriptors for pull stations do not match point descriptions on the plan, AC power loss is incorrectly identified as NAC trouble, the duct detectors activate a general alarm condition. Need to provide list of signals recieved by remote monitoring of test activity today at next inspection. Notification devices tested okay.
INSP-Final Inspection7/24/20067/24/20067/24/2006PCANC
DetailsTroy Cobbley