Permit NumberFIR06-00314
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 5204 W FRANKLIN ST
Project NameSPR NICK-N-WILLY'S PIZZA
Customer Number918730501
ePlanReview 
Description
NICK-N-WILLY'S WORLD FAMOUS TAKE-N-BAKE PIZZA-FRED MEYER BLDG * This building is fully fire sprinklered. To relocate 3 existing SSP's, plug 2 existing SSP's and replace 1 Dry Pendant with a new Dry Pendant in a new (replaced?) walk-in cooler. Fire sprinkler work is related to the interior remodel with demolition and installation of new interior walls to a former ice cream shop for a new carry out take and bake pizza sales tenant in an existing 1,148-ft/2 space. This space is located in the Fred Meyer building. The fire sprinkler system work shall comply with IFC 2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD06-00904.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/15/20066/16/20066/16/2006APASS
DetailsForrest France
Fire sprinkler work is acceptable, one HVAC register to be relocated a min. 1' away from a pendent at the west side-to be verified at life safety final.
INSP-Sprinkler Rough-in/Hydro6/6/20066/7/20066/7/2006APASS
DetailsTroy Cobbley
Sprinkler rough-in passed. Some of the drops are overspaced by a few inches. These sprinklers are on 15' long drops which once tile is in may be spaced correctly. This will be checked at final.