Permit Information
Permit NumberFIR06-00317
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 1299 N ORCHARD
Project Namealm - SYRINGA BANK-BASEMENT
Customer Number 
ePlanReview 
Description
To provide total notification in the TI space located in the basement. A new NAC panel will be installed in the same location of the existing FACP (existing smoke detector) to accommodate the new visual circuit. The horn circuit is fed from the FACP. No written comments. Battery calculations appear to be sufficient. Provide revised building map, including any architectural changes to the PDS Fire Inspector at time of inspection.

The associated building permit (BLD06-00522) is to remodel a 940 sq.ft. area in the basement for a 608 sq ft office space and a 332 sq ft computer server room. Work to include construction of noncombustible partitions, relocation of a door, installation of ceiling and lighting, miscellaneous related finishes. This building is fully fire sprinklerd ANY alterations to the sprinkler system shall be installed per NFPA #13 as regulated by the fire department. Rmh (Beck construction RCE-3198)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/24/20066/26/20066/26/2006APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection6/20/20066/21/20066/21/2006AFAIL
DetailsTroy Cobbley
Strobes are mounted too low and candella is wrong. See plans for locations.