Permit Information
Permit NumberFIR06-00328
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 10943 W EXECUTIVE DR
Project NameSPR JOHNSTONE SUPPLY
Customer Number 
ePlanReview 
Description
Johnstone Supply - To install a complete overhead fire sprinkler system incorporating High Piled Combustible Storage, Ordinary Hazard and Light Hazard Occupancy protection in a new 34,160-ft/2, one story office, retail and warehouse building with a 2,660-ft/2 mezzanine. This building is constructed of concrete tilt-up exterior walls, concrete slab floor, steel mezzanine floor and steel bar joist roof and metal studs. The underground fire service supply was permitted under FIR056-00795. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD05-02089.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/1/20069/5/20069/5/2006APASS
DetailsForrest France
Required corrections have been made, fire sprinkler permit finaled.
INSP-Final Inspection8/30/20069/1/20069/1/2006APART
DetailsForrest France
Final field inspection is satisfactory pending proper coverage at the level of exit discharge for two stairways.
INSP-Sprinkler Rough-in/Hydro8/21/20068/22/20068/22/2006PPASS
DetailsTroy Cobbley
Sprinkler rough-in is passed. Piping in the office areas is ok to cover. Two esfr heads on the east side of the electrical room are overspaced. Earthquake bracing on the mains needs finished up. Above ground hydro test passed.
INSP-Sprinkler Rough-in8/8/20068/9/20068/9/2006PPASS
DetailsTroy Cobbley
Riser room and the electrical room piping rough-ins are passed and the piping can be covered.
INSP-Sprinkler Rough-in7/17/20067/18/20067/18/2006PPASS
DetailsTroy Cobbley
The sprinkler piping as marked on the plans that is located above the ceilings is ok to cover.