Permit Information
Permit NumberFIR06-00346
StatusFinaled
Name MICRON TECHNOLOGY INC FP
Site Address 8000 S FEDERAL WAY
Project NameSPR MICRON #24C F4 FAB
Customer NumberC8790
ePlanReview 
Description
MICRON BUILDING #24C - (C8790) - To install fire sprinkler protection under the raised floor of new 100 lineal feet of 4'-6" and 8'-0" wide by 4'-0" deep reinforced concrete equipment trenches at the subfab and the cleanroom ceilings, for the remodel of Fab 4A in Building 24C to accommodate new tool sizes and equipment. The fire sprinkler work relate to subfloor trench work, reconstruction of fab clean walls, hepa filter ceiling grids. This work is located in Building #24C between grid lines #18 & 25 and #D & F at an approximate 6,675-ft/2 of the subfab, a 10,280-ft/2 area of the main floor fabrication area and 10,190-ft/2 of the interstitial space. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD06-00475.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/22/20069/27/20069/28/2006PPASS
DetailsForrest France
Fire sprinkler final inspection passed, permit finaled.
INSP-Sprinkler Rough-in/Hydro9/11/20069/12/20069/12/2006APART
DetailsForrest France
Re-test of hydrostatic for the underfloor system passed.
INSP-Sprinkler Rough-in/Hydro9/5/20069/8/20069/8/2006AFAIL
DetailsTroy Cobbley
Hydro test failed. Guage appeared to have lost 2-3 psi from 10:15am to 12:15pm.
INSP-Sprinkler Rough-in/Hydro8/16/20068/17/20068/17/2006APART
DetailsForrest France
Rough-in for the west underfloor area and OH for the 1st and 2nd levels is acceptable, Hydrostatic test for a portion of these systems at the two 4" main trees and one 3" passed.