Permit NumberFIR06-00362
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 2100 E BRANIFF ST
Project NameSPR MOTIVE POWER DPV REPLACE
Customer Number 
ePlanReview 
Description
MOTIVE POWER ANNEX-DPV REPLACEMENT - To replace a defective 4" DPV and B.F. Control with a new 4" Viking Model "F-1" DPV and a 4" Firelock Butterfly control valve. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this permit, to provide witness of compliance verification of meeting minimum code. This permit is not attached to any building permit. This permit is not attached to any building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/2/20106/2/20106/2/2010PPASS
DetailsForrest France
Permit okay for final status.
FIR-Aging Inspection6/1/20106/1/20106/2/2010 DONE
DetailsForrest France
Scheduled for final.
INSP-Conference5/20/20095/21/20095/21/2009ADONE
DetailsTroy Cobbley
I spoke to Adam and told him that an inspector would need to witness that the signals had been corrected and then the permit could be finaled.
INSP-Final Inspection7/18/20077/18/20077/18/2007PFAIL
DetailsTroy Cobbley
The flow switch reported correctly to the remote annunciator and to central station but the tamper and low air reported as general trouble signals. They need to be supervisory. The trip test of the valve passed.
FIR-Aging Inspection2/20/20072/20/20072/27/2007 DONE
DetailsForrest France
Contractor to schedule inspection.