Information based on query as of Friday, August 16, 2024.
Permit Information
Permit NumberFIR06-00365
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 412 S 13TH ST
Project NameSPR OH PLAZA MIXED USE BSMT PA
Customer Number 
ePlanReview 
Description
PLAZA MIXED USE-BASEMENT PARKING GARAGE - OH (Basement parking garage phase only) - To install an OH-1 wet, gridded overhead fire sprinkler system with SSP's (Dry Pendants) in a new 30,000-ft/2 basement parking garage. The underground fire service supply is under separate permit FIR06-00262. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD05-00926.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/26/20083/26/20083/26/2008APASS
DetailsForrest France
Noted corrections are complete, fire sprinkler permit finaled.
INSP-Final Inspection3/20/20083/21/20083/21/2008AFAIL
DetailsForrest France
Missing ceilings at some locations, need missing escutcheons installed, noted sprinkler head adjacent to the elevator equipment panel must be located within 2' of the heat detector for shunt trip per state elevator requirements.
INSP-Final Inspection3/18/20083/18/20083/18/2008PDEFR
DetailsForrest France
Wrong permit number requested for inspection.
INSP-Final Inspection3/13/20083/14/20083/14/2008APART
DetailsForrest France
Noted this is the wrong permit number requested for inspection-apparently intended for overhead work for the phase two building. Completed sprinkler monitoring testing for flows, tampers and floor control valves, noted one painted head at the first floor entryway, no other areas inspected at this time.
INSP-Final Inspection2/12/20082/12/20082/13/2008PPART
DetailsForrest France
1st floor walkthrough of the apartment units only -noted 401's have been added at various locations to avoid light fixture obstructions, painted heads indicated at the previous visit have been replaced as necessary.
INSP-Final Inspection1/30/20081/31/20081/31/2008APART
DetailsForrest France
Preliminary walkthrough of the 1st and 5th floor units only, noted painted heads at some locations will not be accepted-heads cannot be cleaned but must be replaced due to paint at the seat or element-see units 102 and 505 for typical examples, also noted final head locations cannot be approved at this time due to missing lights and fixtures not yet installed for verification of proper clearances from obstructions.
INSP-Final Inspection1/15/20081/16/20081/16/2008ACANC
DetailsForrest France
bruce Note: 2, 3, and 4 Phone #: ###-####
INSP-Sprinkler Rough-in1/14/20081/15/20081/15/2008APART
DetailsForrest France
Corrections noted at the previous inspection are complete, final pending ceiling tile and escutcheons, will also need plans at next inspection for final review.
INSP-Final Inspection1/10/20081/11/20081/11/2008AFAIL
DetailsForrest France
Coverage is obstructed by structural columns at five locations.
INSP-Final Inspection5/1/20075/1/20075/1/2007 PART
Approved for TOC. Ceiling and heating provisions not installed in bsmt parking area; sprinkler installation not completed in Phase two bsmt parking area.
FIR-Aging Inspection2/20/20072/20/20072/23/2007 DONE
DetailsForrest France
Project is under construction, work in progress.