INSP-Final Inspection | 11/29/2007 | 11/30/2007 | 11/30/2007 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. The slave dialer has the required 24 hour battery backup.
|
INSP-Final Inspection | 11/7/2007 | 11/14/2007 | 11/14/2007 | A | FAIL |
Troy Cobbley
|
|
|
As per the previous correction notice plans need to be resubimitted showing the dact connected to the facp, fix the trouble signal on the facp, adjust and retest the tamper switches, provide updated map at the facp
|
INSP-Final Inspection | 6/21/2007 | 6/26/2007 | 6/26/2007 | A | FAIL |
Troy Cobbley
|
|
|
The only item that tested ok was the duct smoke detector in the Lucent tenant space. The plans need to be resubmitted showing the slave radionics dialer that has been connected to the Simplex 4005 panel. The dialer is not sending out phone line troubles or loss of battery. It did however send out the duct detector supervisory and the loss of ac power. A building map needs to be provided and the power supply for the dialer needs to be mechanically secured. No other duct detectors were tested or any of the sprinkler devices. Test has been stopped and failed.
|
FIR-Aging Inspection | 9/8/2006 | 9/8/2006 | 9/15/2006 | | NR |
Troy Cobbley
|
|
|
Per Charlie the work is complete, they are just waiting to get the st. als project completed first
|