Permit Information
Permit NumberFIR06-00367
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 9939 W EMERALD ST
Project Namealm - WESTPARK BLD "C"
Customer Number 
ePlanReview 
Description
To upgrade a required sprinkler monitoring fire alarm system to allow monitoring of the required smoked duct detectors per IFC 907.11. Eleven duct detectors will be installed under this permit. This permit was initiated after a correction notice was left by PDS Fire Inspector Troy Cobbley (dated 4/3/2006), based upon an aging building permit.

The associated building permit (BLD 02-02216) is to remodel an existing 6,827 sq.ft. office tenant by converting 2 offices into one 650 sq.ft. conference room per approved plans on file. Work to involve construction of interior noncombustible partitions installation of double doors and safety glazing sidelights. NOTE: This building is fully fire sprinklered any alterations or modifications to the fire sprinkler heads shall be per NFPA #13 as regulated by the fire department. (pc#602-02) rmh (LAM RESEARCH)(WESTPARK BLD "C")
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/29/200711/30/200711/30/2007APASS
DetailsTroy Cobbley
Permit finaled. The slave dialer has the required 24 hour battery backup.
INSP-Final Inspection11/7/200711/14/200711/14/2007AFAIL
DetailsTroy Cobbley
As per the previous correction notice plans need to be resubimitted showing the dact connected to the facp, fix the trouble signal on the facp, adjust and retest the tamper switches, provide updated map at the facp
INSP-Final Inspection6/21/20076/26/20076/26/2007AFAIL
DetailsTroy Cobbley
The only item that tested ok was the duct smoke detector in the Lucent tenant space. The plans need to be resubmitted showing the slave radionics dialer that has been connected to the Simplex 4005 panel. The dialer is not sending out phone line troubles or loss of battery. It did however send out the duct detector supervisory and the loss of ac power. A building map needs to be provided and the power supply for the dialer needs to be mechanically secured. No other duct detectors were tested or any of the sprinkler devices. Test has been stopped and failed.
FIR-Aging Inspection9/8/20069/8/20069/15/2006 NR
DetailsTroy Cobbley
Per Charlie the work is complete, they are just waiting to get the st. als project completed first