INSP-Final Inspection | 9/28/2006 | 9/28/2006 | 9/28/2006 | P | PASS |
Forrest France
|
|
|
Corrections at fire doors are complete, fire alarm permit finaled.
|
INSP-Alarm Testing | 9/26/2006 | 9/27/2006 | 9/27/2006 | A | PART |
Forrest France
|
|
|
Remainder of fire alarm work passed inspection except one pair doors on the main level which failed to properly close upon activation of the adjacent smoke detector.
|
INSP-Sprinkler Rough-in/Hydro | 9/20/2006 | 9/26/2006 | 9/26/2006 | A | PART |
Forrest France
|
|
|
Tested notification devices for the basement, 1st floor and mezzanine levels, need to replace two strobe only with horn/strobes as the decible level is too low in one area as discussed, tested vesda systems for zones 1-4, tested two duct detectors for zone 5 and one sd for door hold open at the main level. Concluded inspection at this time due to time constraints, basement detection and new h/s to be verified at next visit.
|
INSP-Alarm Testing | 9/14/2006 | 9/21/2006 | 9/15/2006 | A | CANC |
Forrest France
|
|
|
Complete testing of all fire alarm devices within the B24C project 8790 remodel area at all levels.; Phone #: ###-#### Internet Inspection Request from: Greg Kirkes Inspection cancelled from web by: Greg Kirkes
|
INSP-Sprinkler Rough-in/Hydro | 9/8/2006 | 9/12/2006 | 9/12/2006 | A | DEFR |
Forrest France
|
|
|
Inspection request was intended for the fire sprinkler permit portion of this project, not fire alarm at this time.
|