Permit Information
Permit NumberFIR06-00436
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 6455 S EISENMAN RD
Project NameSPR HARRIS AUTO SALES FACILITY
Customer Number 
ePlanReview 
Description
HARRIS AUTO SALES FACILITY - To fully fire sprinkler with an OH-2 Occupancy fire sprinkler system in a 6,210-ft/2, two story type V-B auto sales facility with maintenance shop and wash bay. The 1st floor is 2768-ft/2 and the 2nd floor is 3442-ft/2. Fire sprinklers used for story increase. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The underground fire service supply is being installed FIR06-00126. This permit is attached to building permit: BLD05-01823.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/6/200611/6/200611/6/2006PPASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Sprinkler Rough-in/Hydro10/18/200610/18/200610/19/2006PPART
DetailsForrest France
AG hydrostatic test for the antifreeze system, wet system, and FDC piping passed. Noted one missing head at the lower stair landing.
INSP-Sprinkler Rough-in/Hydro7/11/20067/12/20067/12/2006APASS
DetailsTroy Cobbley
Underground hydro test passed