Permit Information
Permit NumberFIR06-00474
StatusExpired
Name PEAK ALARM
Site Address 2000 E YAMHILL RD
Project NamealmIdaho Truss express move-in
Customer Number 
ePlanReview 
Description
To provide a new required sprinkler monitoring system to an existing building. One flow, two control valves, smoke above panel, manual pull and two (2) duct smoke detectors for HVAC shutdown (it appears the duct detectors are existing, no cut sheets provided, so they should be per the code in which they were installed). No written comments. Battery calculations appear to be sufficient. Provide building map, including any architectural changes to the PDS Fire Inspector at time of inspection.

The associated building permit (BLD06-01235) is to remodel an office area located on the mezzanine of an existing 39,192 sq ft building to be used for manufacturing wall panels per approved plans. Work to include removal of non bearing interior partitions to create open office area, construct a new exit stairway from the mezzanine to the exterior of building, to construct a new handicap accessible ramp to the front entrance. Miscellaneous related finishes. This building is fully fire sprinklered any alterations to the sprinkler system shall be per NFPA #13 as regulated by the fire department. Rmh (NO CONTRACTORS REGISTRATION PROVIDED. APPLICANT CERTIFIES EXEMPTION PER IDAHO STATUTE 54-5205)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Expired6/11/20106/11/20106/11/2010PPASS
DetailsForrest France
Tenant has relocated, building is vacant. Permit expired- IFC 2006 sec. 105.3.1
FIR-Aging Inspection6/7/20106/7/20106/11/2010 DONE
DetailsForrest France
Site visit completed.
FIR-Aging Inspection3/27/20083/27/20083/28/2008PDONE
DetailsForrest France
Peak alarm to schedule testing for final acceptance of permit work.
INSP-Sprinkler Rough-in6/30/20067/3/20067/3/2006APART
DetailsForrest France
Preliminary alarm inspection to verify functionality of the new FA panel. Alarm work per the scope of the permit is not yet completed at this time. Testing done today included panel batteries, phone lines, tampers at riser, wet flow, outside bell, and signal verification. AC power loss did not report to monitoring company as required, also need to provide a lock at the breaker. Remainder of alarm work to be tested at next inspection.