INSP-Final Inspection | 2/23/2007 | 2/26/2007 | 2/26/2007 | P | PASS |
Forrest France
|
|
|
Corrections are complete, fire sprinkler permit finaled.
|
INSP-Final Inspection | 2/22/2007 | 2/23/2007 | 2/23/2007 | P | NR |
Forrest France
|
|
|
Per phone call from the contractor, the required repairs have not yet been made.
|
INSP-Final Inspection | 2/21/2007 | 2/22/2007 | 2/22/2007 | P | FAIL |
Forrest France
|
|
|
The outside bell failed to function upon waterflow. UG flush completed okay.
|
INSP-Final Inspection | 1/29/2007 | 1/30/2007 | 1/30/2007 | P | NR |
Forrest France
|
|
|
Contact is James @ ###-####. Thanks Phone #: ###-#### Contractor is not ready per phone call, pending UG flush.
|
INSP-Final Inspection | 1/25/2007 | 1/29/2007 | 1/29/2007 | P | NR |
Forrest France
|
|
|
Noted the UG supply line flush must be completed prior to overhead final.
|
INSP-Final Inspection | 1/4/2007 | 1/5/2007 | 1/5/2007 | A | CANC |
Forrest France
|
|
|
Please call Brian one hour before arriving.
His number is ###-####. Thanks Phone #: ###-#### Inspection cancelled from web by: Stan Beus
|
INSP-Sprinkler Rough-in | 7/28/2006 | 7/31/2006 | 7/31/2006 | P | PART |
Forrest France
|
|
|
OH rough-in is okay to cover, noted two sprinkler heads in the basement which will require relocation for proper spacing and coverage.
|
INSP-Sprinkler Rough-in | 7/27/2006 | 7/28/2006 | 7/28/2006 | A | FAIL |
Forrest France
|
|
|
Relocate one head at basement closet, one drop is overspaced at basement room, tenting is not adequate at three riser locations on swing joints and is missing above branch lines in the family room, discussed freeze protection for lines in the garage area.
|