Permit Information
Permit NumberFIR06-00485
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 210 N MILWAUKEE ST
Project NameSPR CAFE OLE'
Customer Number 
ePlanReview 
Description
OLE INTERNATIONAL FOODS CORP - To install the underground fire service supply and the complete overhead sprinkler system, designed for Light and OH-1 occupancy throughout this existing restaurant. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. A riser room shall be constructed under a required building permit for the enclosure of the system riser prior to this permit acceptance/final. This permit is currently not attached to any building permit at this date. BLD06-0328409/28/07 Revised Scope of Work:
These plans and calculations were resubmitted as-built for review. Changes are noted as Revision #2, dated 06/08/07. An outline of the revisions dated 08/29/07, has been submitted as an attachment to these plans reviewed
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/30/200710/30/200710/30/2007PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro10/30/200710/30/200710/30/2007PCANC
DetailsTroy Cobbley
please call russ to confirm time Phone #: ###-#### Internet Inspection Request from: Jeff Packham Inspection cancelled from web by: Jeff Packham
INSP-Sprinkler Rough-in/Hydro6/8/20076/8/20076/8/2007PPASS
DetailsTroy Cobbley
Above ground hydro test passed.
INSP-Sprinkler Rough-in/Hydro6/7/20076/7/20076/7/2007PFAIL
DetailsTroy Cobbley
Above ground hydro test failed.
INSP-Sprinkler Rough-in/Hydro5/31/20076/1/20076/1/2007APART
DetailsTroy Cobbley
See the city approved plans for locations where sprinklers need to be added and insulation reattached to the roof deck. The sidewall sprinklers at the main entrance are too far from the deck. As-builts need to resubmitted showing the added line in the dining/remote area.
INSP-Final Inspection5/4/20075/4/20075/4/2007PPART
DetailsTroy Cobbley
A temporary occupancy was given by dave hanniman for the new areas to be occupied while the fire alarm and fire sprinkler systems are finished being installed.
INSP-Final Inspection5/4/20075/4/20075/4/2007PCANC
DetailsTroy Cobbley
Phone #: ###-#### Internet Inspection Request from: Jeff Packham Inspection cancelled from web by: Jeff Packham
FIR-Aging Inspection10/12/200610/12/200610/12/2006 NR
DetailsTroy Cobbley
work is in progress per Jeff