Permit NumberFIR06-00523
StatusFinaled
Name PROTEX
Site Address 2970 W ELDER ST
Project NameCAMBRIA SUITES
Customer Number 
ePlanReview 
Description
To install a new manual and automatic fire alarm system including monitoring the AFS system, smoke dampers control, air handlers shut-down, elevator recall and monitoring the future cooking hood suppression system. Ref building permit BLD 05-02392.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/4/20074/4/20074/4/2007PPASS
DetailsForrest France
The remainder of correction notice items have been verified for compliance, final fire alarm inspection passed, permit finaled.
INSP-Alarm Testing4/3/20074/3/20074/3/2007PPART
DetailsForrest France
See comments per field inspection completed by M. Timmerman.
INSP-Alarm Testing4/2/20074/2/20074/2/2007PFAIL
DetailsForrest France
See comments per inspection completed by M. Timmerman.
INSP-Alarm Testing3/30/20073/30/20073/30/2007PDEFR
DetailsForrest France
Field inspection performed by M. Timmerman.
INSP-Alarm Testing3/28/20073/29/20073/29/2007AFAIL
DetailsForrest France
FA inspection for the 4th floor only completed today, some defficiencies corrected while on site, other items in need of repair include non-functional SD 105 in the corridor, one SD at the SW corridor is overspaced, the fire damper at the north hall does not operate correctly, vending area lacks sufficient detector coverage, as-built plans do not show the deletion of two FD's.
INSP-Alarm Testing3/28/20073/28/20073/28/2007PPART
DetailsForrest France
Sprinkler monitoring only tested today, noted addressing at the WF switches in the riser room to correctly identify the system served.
INSP-Alarm Testing3/26/20073/27/20073/27/2007ANR
DetailsForrest France
Noted several items in need of correction including location and spacing of initiation and notification devices, cd ratings, manual pull station to be relocated, elevator monitoring, panel must be clear of all sprinkler supervisory signals prior to testing, missing signage at door to the FACP, etc.
INSP-Conference3/20/20073/21/20073/21/2007ADONE
DetailsForrest France
Regarding FA plans matching floorplan.
INSP-Conference2/21/20072/22/20072/22/2007ADEFR
DetailsForrest France
To be completed 2/23.