Permit Information
Permit NumberFIR06-00536
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 6017 W FAIRVIEW AVE
Project NameLes Schwab Warehouse
Customer Number 
ePlanReview 
Description
Scope of Work: Run a new 8" fire service through a utility vault with a new back flow deice and then up and into an existing 5,000 ft/2 single story warehouse. A Peerless Fire Pump Unit / Riser will be installed. The overhead piping will consist of a 4" wet fire sprinkler system, protecting Rack tire storage to 15'-0", incorporating EFSR heads. The water supply will be connected to a new Peerless, 65 psi/1000 gpm rated electric booster pump, and a (current) United Water supply of 60 static, 1,750 gpm flow @ 20 psi. The building is fully fire sprinklered with an unlimited area designation. Any racking over 15'-0" will require separate plans and permits prior to installation. This permit is not attached to a building permit; proposed work is as a result of a fire dept inspection report.Revised Scope of Work:
The revision of the original scope of work includes relocating the FDC to the NW corner of the Bldg. as indicated on sheet FP-101. The new location meets code.
Submittals Of The Following Items Are Required:
The outline of the structure is not clearly defined. FP-101 & FP-102
(Revised & Clarified 11/16/2006)
The notes regarding the scope of work need to be clarified. FP-101 & FP-102
(Revised & Clarified 11/16/2006)
Please provide the notes that pertain to the Fire Pump Schematic.
(A sheet FP-3 has been submitted for clarity 11/16/2006)
Please provide Warehouse area ft/2 and construction type. FP-100
(Revised & Clarified 11/16/2006)
Provide a trapeze detail. Include the design modulus.
(Revised & Clarified 11/16/2006)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/11/20075/14/20075/14/2007APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection5/9/20075/11/20075/11/2007AFAIL
DetailsTroy Cobbley
The fire pump acceptance test passed. Fire sprinkler rough-in passed. Contractor supplied certification that the fire pump package had been hydro tested. The backflow was certified as I waited. To final the project the signage on the riser room door needs to be installed and the orfice to test the flow switch needs to be provided. The ventilation and drainage as is will be acceptable. Emergency lighting has been provided.
INSP-Sprinkler Rough-in5/2/20075/2/20075/2/2007PPASS
DetailsTroy Cobbley
hydro test of the fdc passed.
INSP-Sprinkler Rough-in/Hydro4/26/20074/27/20074/27/2007APASS
DetailsTroy Cobbley
Hydro test of the overhead piping is passed. Fire pump and fdc stills needs hydro testing
INSP-Supply line flush4/12/20074/13/20074/13/2007APASS
DetailsTroy Cobbley
Underground flush and hydro test passed.
INSP-Supply line flush4/10/20074/11/20074/12/2007APASS
DetailsTroy Cobbley
Underground supply line is ok to cover. The underground vault has been deleted as well as the remote FDC. I notified the fire sprinkler contractor that approval is required for the relocation of the FDC.
INSP-Supply line flush4/10/20074/11/20074/11/2007PCANC
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 4/10/2007 at 8:22:07 AM. Contact: ###-####.
INSP-Supply line flush4/10/20074/12/20074/10/2007ACANC
DetailsTroy Cobbley
###-#### George Inspection cancelled from web by: Patricia Smith