Permit Information
Permit NumberFIR06-00548
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 7316 W FAIRVIEW AVE
Project NameGold's Gym @ Fairview
Customer Number 
ePlanReview 
Description
The scope of work begins at an existing flange above finished floor. A wet pipe system is designed to protect the entire bldg. The design criteria is of Light Hazard protection.
The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD06-03295.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/21/200612/22/200612/22/2006PPASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in/Hydro12/21/200612/21/200612/21/2006PPASS
DetailsTroy Cobbley
The overhead hydro test passed.
INSP-Sprinkler Rough-in/Hydro12/19/200612/20/200612/20/2006AFAIL
DetailsTroy Cobbley
Overhead hydro test failed.
INSP-Sprinkler Rough-in12/7/200612/8/200612/8/2006APASS
DetailsTroy Cobbley
Gave approved for piping to be covered above hardlids next to pool at the extended coverage heads and in the east stairwell. No ceilings had been originally shown on plans for the stairwell.
INSP-Sprinkler Rough-in11/30/200612/1/200612/1/2006PPART
DetailsForrest France
Inspection for cover at the drop ceilings in the tanning booth rooms, mens locker and womens locker- one head in the laundry room is overspaced off an adjacent wall, one head in the mens locker west side is overspaced, painted heads in the womens locker room to be replaced as discussed, remainder of ceilings in these areas inspected today are okay for cover.
INSP-Sprinkler Rough-in/Hydro11/17/200611/17/200611/17/2006PPASS
DetailsTroy Cobbley
See city approved plans for hardlid areas marked with an "OK" that the sprinkler piping is ok to cover.
INSP-Sprinkler Rough-in9/22/20069/25/20069/25/2006APART
DetailsForrest France
Sprinklers at the hard lid ceilings in the womens locker room as marked on approved plans are okay to cover.
INSP-Sprinkler Rough-in9/15/20069/18/20069/18/2006APASS
DetailsTroy Cobbley
Hard lid areas in the northwest corner as marked on the plans are ok to cover