Permit NumberFIR06-00562
StatusFinaled
Name M2 AUTOMATION
Site Address 150 N CAPITOL BLVD
Project NameCITY HALL
Customer Number 
ePlanReview 
Description
To add required devices to both elevators to bring shunt trip/recall and Firemans's hat annunciation up to current code.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/24/200710/25/200710/25/2007APASS
DetailsForrest France
Final inspection passed per K. Roule, fire alarm permit finaled.
INSP-Final Inspection10/21/200710/23/200710/23/2007APART
DetailsForrest France
Building one elevator testing passed, final pending building two elevator recall functional test, all other items are acceptable.
INSP-Final Inspection10/12/200710/16/200710/16/2007APART
DetailsForrest France
One HD at building one elevator equip penthouse is not functional, shunt trip and voltage monitoring at bldg. 2 elevator tested okay. Need to test recall at both elevators, retest one HD, and review approved plans at next inspection.
FIR-Aging Inspection3/2/20073/2/20073/5/2007 DONE
DetailsForrest France
wip