Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR06-00596
StatusFinaled
Name PROTEX
Site Address 495 S CAPITOL BLVD
Project NameBODO BLDG #8-ALM
Customer Number 
ePlanReview 
Description
To provide the remainder of the required manual fire alarm system and all items required for a high rise, which will include fire department communication, voice/evac, manual pull stations, HVAC shutdown, elevator recall/shutdown, sprinkler, fire pump and secondary water supply monitoring, fire/smoke damper controls, door release and required automatic detection for floors 4 through 11 and the roof of the building (Hampton Inn). This permit may NOT be finaled until FIR05-00695 has been finaled.

FIR05-00695 was issued as a partial under the shell permit BLD04-02876. This permit was to install the fire alarm system for the parking structure only, partial ground floor, to include a 2-hour rated corridor for fire department access to the Fire Command Center, located on the ground floor. Floors 2 and 3 will be completed. Elevator #4, which serves the ground floor to 4th floor only will be installed and in service. The 4th floor will not be utilized at this time for public use.

The associated building permit (BLD 05-01077) is to finish the tenant improvement for the new 235,965 square foot, eleven story high rise, parking and Hampton Inn hotel portion of this building. The first floor contains 7,775 sq. ft. of retail space (to be finished under separate tenant improvement permits), 9,000 sq. ft. of hotel lobby space and 19,020 sq. ft. of parking garage space (total 35,795 sq. ft.). The second, third and fourth floors are parking garage (34,750 sq. ft. each floor, total of 104,250 sq. ft.). The fifth floor contains hotel rooms, laundry, meeting rooms, exercise room and indoor swimming pool (16,000 sq. ft.). The sixth through eleventh floors contain hotel guest rooms (13,320 sq. ft. per floor, total 79,920 sq. ft.). The fire-resistance rating reductions allowed by IBC, Sections 403.3.1 and 403.3.2 is being used to reduce the required fire-resistive rating from Type IB to Type IIA. The reduction is allowed in this building with the use of sprinkler control valves equipped with supervisory initiating devices and water-flow initiating devices for each floor. The other requirement of this reduction is the construction of two-hour fire-barriers between the first floor mercantile occupancies and the remainder of the building. All construction per the approved plans and attached comment list. JCM BODO BLDG #8-Hampton Inns Hotel/Garage (Tenant Completion) per Cody R. no TEMP occupancy until the DR requirements are met. Exterior Paint color not correct.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/9/20072/12/20072/13/2007APASS
DetailsTroy Cobbley
Per Mike Timmerman this permit can be finaled.
INSP-Final Inspection2/9/20072/9/20072/9/2007PCANC
DetailsTroy Cobbley
Verify completion of c/n items Phone #: ###-#### Inspection cancelled from web by: Terry Owsley
INSP-Alarm Testing1/31/20072/1/20072/1/2007PPART
DetailsForrest France
Need to retest elevator recall functions, the manual pull stations at the first floor lobby are installed above max. allowable height AFF, the tamper switch at the OS&Y @ tank suction is not functional, need to provide an additional module for the tank fill level monitoring, provide current as-builts and map at the panel, covers at SD shall be removed prior to final permit approval.
INSP-Alarm Testing1/18/20071/18/20071/18/2007PPART
DetailsForrest France
Inspection for the 5th floor HD's, added SD in the meeting storage room, and testing for the common corridor detection devices completed today.
INSP-Alarm Testing1/16/20071/17/20071/17/2007APART
DetailsForrest France
Partial inspection for the 5th floor completed today including guest rooms, meeting rooms, laundry service and employee areas, and guest services. Need to provide an additional SD in the meeting storage room due to beam obstruction, testing of SD's in the common corridors pending clean hall conditions, heat detectors not tested at this time, programming issue at room 512 repaired while on site, elevator lobby and sprinkler floor controls remain to be tested, EOL, pulls, dampers, DH, and notification tested okay.
INSP-Final Inspection1/10/20071/16/20071/16/2007PCANC
DetailsForrest France
No time to complete inspection due to high volume of scheduled requests.
INSP-Final Inspection1/10/20071/11/20071/10/2007PCANC
DetailsForrest France
this is rafe''s cell. the inspection is for the 5th floor Phone #: ###-#### Inspection cancelled from web by: Terry Owsley
INSP-Final Inspection11/30/200612/1/200612/1/2006PDEFR
DetailsForrest France
Per phone call from contractor, inspection rescheduled for 12/4.
INSP-Alarm Testing10/18/200610/20/200610/20/2006ANR
DetailsForrest France
rob - note: fire alarm only - 6th floor ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith Sufficient visual notification coverage at ADA room 10x cannot yet be determined due to missing room finishes and hardware, door holders are not ready for inspection, elevator is not ready for inspection. Coverage at the SW ADA room and adjacent corridor is acceptable.
INSP-Final Inspection10/17/200610/19/200610/19/2006ADEFR
DetailsForrest France
Per contractor, inspection to be rescheduled for 10/20 as discussed.