Permit Information
Permit NumberFIR06-00621
StatusFinaled
Name MICRON TECHNOLOGY INC FA
Site Address 8000 S FEDERAL WAY
Project Name 
Customer NumberC9454
ePlanReview 
Description
Fire Alarm System: C9454 B02 The existing Pyrotronics fire alarm control panel in Building 2 is aging and ready to be replaced. The Pyrotronics fire alarm control panel will be replaced with a new Edwards control panel. All associated initiating devices will also be replaced with Edwards devices. The existing Pyrotronics System 3 horn panel will remain, along with the notification appliances. Notification coverage for the buiding will be brought up to code in the process.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/25/200811/26/200811/26/2008APASS
DetailsForrest France
Fire alarm permit finaled.
INSP-Final Inspection11/24/200811/25/200811/25/2008ADEFR
DetailsForrest France
Please call 30 min prior to arrival. Phone #: ###-#### Internet Inspection Request from: Jeff Walton
INSP-Final Inspection10/31/200811/4/200811/5/2008APART
DetailsForrest France
Remainder of notification devices including adjustments at the 2nd floor mechanical rooms passed field testing.
INSP-Alarm Testing10/27/200810/30/200810/30/2008APART
DetailsForrest France
Fire alarm notification devices tested okay at the 2nd floor mechanical room areas, common corridor, restrooms, locker room and mech. penthouse, EOL voltage is satisfactory,
INSP-Alarm Testing10/27/200810/29/200810/30/2008APART
DetailsForrest France
Testing for initiating devices at the cleanroom areas photo bays 8 and 9 including manual pull stations, heat detectors, UF smoke detectors, and door release completed satisfactory.
INSP-Alarm Testing10/20/200810/23/200810/23/2008ACANC
DetailsForrest France
Please call 30 min prior to arrival. Phone #: ###-#### Internet Inspection Request from: Jeff Walton Inspection cancelled from web by: Jeff Walton
INSP-Alarm Testing10/20/200810/21/200810/21/2008APART
DetailsForrest France
Testing completed for 2nd floor mechanical area duct smoke detection devices, noted sample tube at one location missing end plug, three units not available for shutdown, also tested flow switch and two DD at the penthouse mechanical room. Additional SD at the 1st floor corridor tested okay.
INSP-Alarm Testing10/10/200810/16/200810/16/2008APART
DetailsForrest France
Tested smoke detectors at and above ceilings including door release and manual pull stations at the common corridors 1st and 2nd floors and electrical/mechanical areas on the 2nd floor. Noted overspaced smoke detection at the west 1st floor corridor and one incorrect address.
INSP-Alarm Testing10/3/200810/8/200810/8/2008APART
DetailsForrest France
Tested remainder of heat detection devices in building 2 at the non-clean common corridors and mechanical areas.
INSP-Alarm Testing9/26/200810/2/200810/2/2008ADEFR
DetailsForrest France
Inspection request intended for permit FIR06-00620.
INSP-Alarm Testing4/23/20084/29/20084/29/2008APART
DetailsForrest France
Horn and strobe testing completed for the cleanroom areas only, noted locations on plan in need of revision.
INSP-Alarm Testing4/23/20084/28/20084/28/2008APART
DetailsForrest France
Completed preliminary walkthrough of cleanroom areas prior to fire alarm notification test to verify positioning, cd settings and spacing of horn/strobe appliances.
FIR-Aging Inspection3/14/20073/14/20073/16/2007 DONE
DetailsForrest France
work in progress