Permit Information
Permit NumberFIR06-00628
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 6299 N EAGLE RD
Project NameSTAPLES
Customer Number 
ePlanReview 
Description
To install new sprinkler undergound for new retail store buidling. Ref BLD06-01554.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/12/200612/12/200612/12/2006PPASS
DetailsTroy Cobbley
Underground permit finaled
INSP-Final Inspection12/5/200612/6/200612/6/2006PFAIL
DetailsTroy Cobbley
Still need the alarm connections tested. Need two additional tamper switches for the anti-freeze loop backflow preventor per IFC 903.4.1, need forward flush, head wrench, backflow certification, trapeze calcs and wall to deck in the warehouse as per the previous inspection entry.
INSP-Sprinkler Rough-in/Hydro11/7/200611/8/200611/8/2006PPART
DetailsForrest France
AG hydrostatic test of the wet and antifreeze systems are acceptable.
INSP-Sprinkler Rough-in10/19/200610/20/200610/20/2006PPASS
DetailsTroy Cobbley
Overhead sprinkler system rough-in is passed. Contractor needs to provide calculations for the trapeze hangers and provide a full height wall between the office area and the warehouse as shown on the plans.
INSP-Supply line flush10/17/200610/18/200610/18/2006APASS
DetailsTroy Cobbley
Underground flush passed.
INSP-Supply line flush10/16/200610/17/200610/17/2006ACANC
DetailsTroy Cobbley
Contractor is not ready for the underground flush
INSP-Sprinkler Rough-in/Hydro10/16/200610/17/200610/17/2006APASS
DetailsTroy Cobbley
Underground hydro test passed
INSP-Sprinkler Rough-in8/25/20068/28/20068/28/2006PPASS
DetailsTroy Cobbley
Underground piping is ok to bury.