INSP-Final Inspection | 4/9/2007 | 4/10/2007 | 4/10/2007 | A | PASS |
Troy Cobbley
|
|
|
Contact: Todd Phone #: ###-####
|
INSP-Final Inspection | 4/3/2007 | 4/4/2007 | 4/4/2007 | A | FAIL |
Troy Cobbley
|
|
|
need to perform forward flush. trip test of the dry system passed
|
INSP-Final Inspection | 3/30/2007 | 4/2/2007 | 4/2/2007 | A | CANC |
Troy Cobbley
|
|
|
Contact: Todd Phone #: ###-####
|
INSP-Sprinkler Rough-in/Hydro | 3/20/2007 | 3/21/2007 | 3/21/2007 | A | PASS |
Troy Cobbley
|
|
|
24 hour air test on the dry system passed.
|
INSP-Sprinkler Rough-in/Hydro | 3/19/2007 | 3/20/2007 | 3/20/2007 | A | PART |
Troy Cobbley
|
|
|
Air test on the dry system was started at 8:45am with 40 1/2 lbs.
|
INSP-Sprinkler Rough-in/Hydro | 3/1/2007 | 3/2/2007 | 3/2/2007 | A | PART |
Troy Cobbley
|
|
|
Lower area sprinkler piping is ok to cover. Need to remove the plywood from the trusses as discussed. Doghouse area has not been inspected yet.
|
INSP-Sprinkler Rough-in/Hydro | 2/27/2007 | 2/28/2007 | 2/28/2007 | P | PASS |
Troy Cobbley
|
|
|
Above ground hydro test passed.
|
INSP-Sprinkler Rough-in/Hydro | 2/27/2007 | 2/28/2007 | 2/27/2007 | A | CANC |
Troy Cobbley
|
|
|
Contact: Todd Phone #: ###-#### Inspection cancelled from web by: Alicia Pauley
|
INSP-Sprinkler Rough-in/Hydro | 11/14/2006 | 11/15/2006 | 11/15/2006 | P | PASS |
Troy Cobbley
|
|
|
Underground hydro test passed.
|
INSP-Sprinkler Rough-in | 10/19/2006 | 10/23/2006 | 10/23/2006 | A | PART |
Forrest France
|
|
|
UG hydrostatic test for the fire supply line passed for building address 7960. Requested contractor to call in the correct address and permit number for this inspection activity completed today.
|
INSP-Sprinkler Rough-in/Hydro | 9/7/2006 | 9/8/2006 | 9/8/2006 | P | PASS |
Troy Cobbley
|
|
|
Underground supply is ok to bury.
|
INSP-Sprinkler Rough-in/Hydro | 9/7/2006 | 9/8/2006 | 9/7/2006 | A | CANC |
Troy Cobbley
|
|
|
Contact: Todd - Cover Inspection; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|