Permit Information
Permit NumberFIR06-00645
StatusFinaled
Name HONEYWELL INC
Site Address 190 E BANNOCK ST
Project NameST LUKES
Customer Number 
ePlanReview 
Description
Scope: Installation of new fire alarm system components in area of TI per upgrade agreement in 1999. Work includes new addressable signal loop for existing devices and new smoke detectors, duct detectors, door and damper release controls, existing AFS monitoring, visual notification devices, nurse station manual station and new power supply for visual signals. Existing voice/chime notification circuit remains as supplemental system. REF BLD06-01392
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/25/20075/29/20075/29/2007APASS
DetailsForrest France
Final fire alarm testing completed satisfactory, corrections repaired, permit finaled.
INSP-Final Inspection5/23/20075/25/20075/25/2007APART
DetailsForrest France
Verified required corrections, a/v notification tested acceptable, all dampers functioned properly except #77 which will need repair and retest, manual pulls and door release are satisfactory, smoke and heat detectors not tested at this time due to time constraints, will test remainder of alarm work at next scheduled inspection as discussed.
INSP-Final Inspection5/21/20075/23/20075/23/2007AFAIL
DetailsForrest France
One a/v in the corridor is non-functional, dampers at two locations in the corridor did not close upon alarm condition, noted one relocated manual pull station is installed too high, one set of double doors is out of adjustment at the mag locks, fire dampers on zone 6 did not function upon smoke detection.
INSP-Final Inspection5/18/20075/21/20075/21/2007ADEFR
DetailsForrest France
Inspection to be rescheduled.
INSP-Alarm Testing11/7/200611/8/200611/8/2006APART
DetailsForrest France
Fire alarm at the waiting area only per field inspection by M.Timmerman is acceptable, noted four damper locations with no access provided to visually confirm closure of the vanes.
INSP-Alarm Testing10/31/200611/1/200611/1/2006PNR
DetailsForrest France
To be rescheduled per contractor as the project is not ready for inspection.