Permit Information
Permit NumberFIR06-00661
StatusFinaled
Name IDAHO FIRE PROTECTION
Site Address 5521 E WARM SPRINGS AVE
Project NameRIVERSTONE SCHOOL GYM
Customer Number 
ePlanReview 
Description
ELLSWORTH KINCAID CONST CORP RCE #6142/Riverstone Community School (Gymnasium) - To install a fire sprinkler system through out the newly constructed 10,650 sq. ft. one story gymnasium building. The starting point for the contractor begins at the property line, providing a new 6" underground service line. The overhead & underground fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD06-00824. This permit is also attached to the underground work permit FIR06-00513.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/28/200612/28/200612/28/2006PPASS
DetailsForrest France
Fire sprinkler passed final inspection, permit finaled.
INSP-Sprinkler Rough-in/Hydro12/27/200612/27/200612/27/2006APART
DetailsForrest France
Overhead hydrostatic test completed, noted one obstructed head in the mech/storage room off the gym.
INSP-Sprinkler Rough-in/Hydro12/20/200612/21/200612/21/2006APART
DetailsForrest France
OH rough-in for the drop ceiling areas is approved for cover, noted upright heads above east restroom hard lids which do not meet spacing requirements, pendent head is to be installed in the drop ceiling now required at the riser room.
INSP-Supply line flush12/20/200612/21/200612/21/2006PPART
DetailsForrest France
UG supply line flush completed satisfactory.
INSP-Supply line flush12/20/200612/21/200612/21/2006ACANC
DetailsForrest France
Duplicate inspection request.
INSP-Sprinkler Rough-in/Hydro10/10/200610/10/200610/10/2006APASS
DetailsTroy Cobbley
Hydro test for the gym area passed. Rough-in for the gym area passed.