Permit Information
Permit NumberFIR06-00677
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 5710 S PAN AM AVE
Project NameSYSCO FOOD SERVICES
Customer Number 
ePlanReview 
Description
SYSCO FOOD SERVICES) To remodel within an existing 124,287 sq. ft., two story office and warehouse building per approved plans. Work includes abandonment of the existing commercial test kitchen and construction of a new 990 sq. ft. test kitchen within an existing warehouse and remodel of existing 2,265 sq. ft. work areas for presentations and conference room areas; construction of a fully accessible restroom & shower; and add 1,256 sq. ft. of storage mezzanine with access stairway above the new test kitchen. New test kitchen approved by Scott Spjute, PDS Planning Mgr., This building is fully sprinklered with 60 foot yards all around per the UBC for unlimited area per last Ada County addition / remodel plans, a copy of which is on file. A "Letter of Compliance" is required for this project as evidence of inspection & approval for code compliance of work done under this permit. The sprinkler scope included adding new piping and heads in the Test Kitchen area and relocating heads in the Presentation area to accommodate a new ceiling layout. Also included is the addition of 5 SSU heads on the second floor in the Office / Mezzanine Storage room. This Fire Sprinkler permit is attached to BLD06-00236
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/12/20071/16/20071/16/2007APASS
DetailsForrest France
Final fire sprinkler inspection passed, permit finaled.
INSP-Sprinkler Rough-in1/4/20071/5/20071/5/2007APART
DetailsForrest France
Sprinkler rough-in is now approved for cover at the kitchen drop ceiling area.
INSP-Sprinkler Rough-in/Hydro12/29/20061/2/20071/2/2007APART
DetailsForrest France
Hydrostatic test for the added piping passed, sprinkler installation is NOT approved for cover at the kitchen area due to obstructions to discharge created by insulation batting adjacent to the upright heads.
INSP-Sprinkler Rough-in11/28/200611/29/200611/29/2006APART
DetailsForrest France
OH rough-in is good for cover at the hard lid ceiling in the restroom only.
INSP-Sprinkler Rough-in10/27/200610/30/200610/31/2006PPART
DetailsForrest France
OH rough-in for cover is okay except as noted on approved plans, one ssu is missing abve the restroom, one head at a new entryway is not yet installed, annular space between the new wall and existing freezer wall may not be properly covered.