INSP-Final Inspection | 1/12/2007 | 1/16/2007 | 1/16/2007 | A | PASS |
Forrest France
|
|
|
Final fire sprinkler inspection passed, permit finaled.
|
INSP-Sprinkler Rough-in | 1/4/2007 | 1/5/2007 | 1/5/2007 | A | PART |
Forrest France
|
|
|
Sprinkler rough-in is now approved for cover at the kitchen drop ceiling area.
|
INSP-Sprinkler Rough-in/Hydro | 12/29/2006 | 1/2/2007 | 1/2/2007 | A | PART |
Forrest France
|
|
|
Hydrostatic test for the added piping passed, sprinkler installation is NOT approved for cover at the kitchen area due to obstructions to discharge created by insulation batting adjacent to the upright heads.
|
INSP-Sprinkler Rough-in | 11/28/2006 | 11/29/2006 | 11/29/2006 | A | PART |
Forrest France
|
|
|
OH rough-in is good for cover at the hard lid ceiling in the restroom only.
|
INSP-Sprinkler Rough-in | 10/27/2006 | 10/30/2006 | 10/31/2006 | P | PART |
Forrest France
|
|
|
OH rough-in for cover is okay except as noted on approved plans, one ssu is missing abve the restroom, one head at a new entryway is not yet installed, annular space between the new wall and existing freezer wall may not be properly covered.
|