INSP-Final Inspection | 8/1/2007 | 8/1/2007 | 8/1/2007 | P | PASS |
Forrest France
|
|
|
Shell fire alarm work passed final inspection, permit finaled.
|
INSP-Final Inspection | 7/31/2007 | 7/31/2007 | 7/31/2007 | P | PART |
Forrest France
|
|
|
Noted items at the previous inspection have been verified for completion, remainder of system testing passed, final pending clear panel-trouble due to a SD in the elevator shaft-need to repair or replace, will sign completion forms when panel is clear.
|
INSP-Final Inspection | 7/25/2007 | 7/26/2007 | 7/26/2007 | A | FAIL |
Forrest France
|
|
|
Lacking notification coverage at the basement restrooms, low air switch is not adjusted properly, identify zone descriptors with central station, missing covers at two control modules, provide lock and label at the breaker to the FACP, provide as-built plans correctly reflecting field mods including deleted monitor points, need map at the panel, 2nd and 3rd floor ID's and elevator not tested at this time, SD at the 2nd floor lobby to be relocated to the drop ceiling.
|
INSP-Final Inspection | 7/23/2007 | 7/25/2007 | 7/25/2007 | A | CANC |
Forrest France
|
|
|
No time available to complete inspection.
|
INSP-Final Inspection | 5/14/2007 | 5/16/2007 | 5/14/2007 | P | CANC |
Forrest France
|
|
|
Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
|
INSP-Final Inspection | 2/27/2007 | 3/1/2007 | 3/1/2007 | P | CANC |
Forrest France
|
|
|
Rafe''s phone. Phone #: ###-#### Inspection cancelled from web by: Terry Owsley
|