Permit Information
Permit NumberFIR06-00710
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 8484 W VICTORY RD
Project NameWELLER PARTS
Customer Number 
ePlanReview 
Description
TVFP scope of work will be to install a complete automatic wet pipe system through out, the new 11,921 ft/2 bldg. The underground work was performed under permit FIR06-00257. This fire sprinkler work shall comply with IFC 2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD06-00569
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/27/20106/1/20106/1/2010APASS
DetailsTroy Cobbley
Jeff and I met at the project and went over the drawings. It appears the 8' isles referenced was a typo since in the design curve "C" was used which covers multiple racks and 4' isles. Permit finaled.
INSP-Final Inspection12/27/200612/28/200612/29/2006APART
DetailsTroy Cobbley
A temporary occupancy was given with dave hannimans permission until the sprinkler design/aisle widths are figured out.
INSP-Sprinkler Rough-in/Hydro12/27/200612/28/200612/28/2006AFAIL
DetailsTroy Cobbley
The rack system overhead hydro test failed. All other items have been corrected. Forward flush passed.
INSP-Final Inspection12/26/200612/27/200612/27/2006ACANC
DetailsTroy Cobbley
bryan ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
INSP-Sprinkler Rough-in/Hydro12/26/200612/27/200612/27/2006AFAIL
DetailsTroy Cobbley
Hydro test failed due to new heads needing added. Atleast one head is needed on the east side of the riser room and another to provide column protection per Chapter 12. Provide flexible couplings for the 4" riser piping at the racks. I notified the general contractor that there can be no storage below the stairs or sprinkler protection will be required. Also there are many screws for the rack piping hangers that are not ran all the way into the supporting structure.
INSP-Final Inspection12/22/200612/26/200612/26/2006ANR
DetailsForrest France
Cancel per phone call from contractor, not ready for inspection due to a split pipe in need of repair.
INSP-Sprinkler Rough-in/Hydro12/22/200612/22/200612/22/2006PFAIL
DetailsTroy Cobbley
The above ground hydro test for both systems failed. But to Brians credit I was unable to make it back to the project in two hours.