Permit Information
Permit NumberFIR06-00713
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 420 W MAIN ST
Project NameVELTEX BLDG-2ND FLR
Customer Number 
ePlanReview 
Description
The sprinkler work consists of adding 7 down heads to accommodate a new clg. layout. The modification does not appear to adversely affect the operation of the existing system. When tenant work affects fire sprinkler protection outside the permitted work area. The affected area sprinkler coverage outside the BLD permit will fall under the Fire Permit scope of work, to maintain the required fire protection within the fire sprinklered facility. The "Riser" and its supplies which include all appurtenances (including tamper, alarm and alarm monitoring) relating to the normal and correct function and integrity of this system will fall under the jurisdiction for code compliant verification.
This permit is attached to BLD06-02002.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/11/200612/12/200612/12/2006PPASS
DetailsForrest France
Items on previous c/n have been verified for completion, inspection passed.
INSP-Final Inspection11/27/200611/28/200611/28/2006AFAIL
DetailsForrest France
Missing retaining straps at beam clamps, beam clamps are not approved to be attatched to pan decking, existing heads above the new drop ceiling shall be removed, one upright at the open area does not match the temp. rating of the adjacent heads, pendent in the break room is off axis.