Permit Information
Permit NumberFIR06-00715
StatusFinaled
Name NORTHWEST SALES COMPANY
Site Address 1555 W SHORELINE DR
Project NameSHORELINE OFFICE BLDG
Customer Number 
ePlanReview 
Description
This project is the installation of a new addressable fire sprinkler monitoring panel and core area A / V notification in conjunction with a tenant improvement being completed on the third floor. The building permit Bld06-01887 AGRI BEEF - SHORELINE OFFICE BLDG - 3RD FLR is to remodel a 9,656 sq.ft office space located on the 3rd floor per approved plans. Work to include, construction of interior partitions to create a new test kitchen, break room, work room, reception area, and two conference rooms, installation of a type one hood system, to upgrade restrooms for accessibility compliance, this building is fully fire sprinklered any alterations to the sprinkler system shall be per NFPA #13 as regulated by the fire department. Rmh
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/4/200712/5/200712/5/2007APASS
DetailsForrest France
Fire alarm upgrade completed for this permit.
INSP-Final Inspection1/26/20071/26/20071/26/2007PPART
DetailsForrest France
Verified elevator voltage monitor and waterflow alarm, permit final pending completion of work scope for the 3rd floor.
INSP-Alarm Testing1/25/20071/25/20071/26/2007PDEFR
DetailsForrest France
Inspection scheduled for 1/26 as agreed.
INSP-Final Inspection1/16/20071/17/20071/17/2007PFAIL
DetailsTroy Cobbley
I gave Don with Russell Corp. permission to use the phase one area of the third floor. See the building approved plans for the exact location marked and signed by me that was inspected. The items remaining include providing an air balance report for the hood and a K class extinguisher. Only the portion of the phase one area on the third floor alarm was tested. The other area was not complete. The lobby areas of the first and second floor fire alarm was tested. This includes the new facp panel, NAC panel, phone lines and elevator recall. See the approved fire alarm prints for devices marked "ok" that have been tested. Signals have been verified as well. Need 120volt monitoring of the elevator power and the correct orfice in the inspectors test connection. Asbuilts will be required to be submitted to the city prior to final.
INSP-Final Inspection1/15/20071/16/20071/16/2007PCANC
DetailsForrest France
No time to complete inspection due to high volume of scheduled requests.