Permit Information
Permit NumberFIR06-00728
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 3501 W ELDER ST
Project NameUNA MAS BLDG
Customer Number 
ePlanReview 
Description
Una Mas Office Shell & Core Building - To construct a 50,280 square foot, three story office building with a 17,420 square foot basement and related site improvements. This building is constructed of a concrete basement, steel structural frame with steel stud exterior walls, metal deck and concrete floors and metal roof deck. The basement contains 27 parking spaces, 14 varying sized storage units, restrooms with showers conference room, mechanical room and circulation hallway. The first floor finished core area includes central corridor/lobby, restrooms, phone/data room. This is a shell and core permit only. Separate tenant improvement permits are required to finish this building for occupancy. This building is fully fire sprinklered. The sprinklers are used for one-hour fire-resistive substitution. The scope of the sprinkler work begins at first flange above finished floor in the basement. From there run a dry pie system out to serve the un-heated spaces. A wet 4” riser will serve through out the remainder of the bldg. providing shell protection only. All sprinkler work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This fire permit is attached to building permit: BLD06-00688. This is a shell and core permit only. Separate tenant improvement permits are required to finish this building for occupancy. The Underground permit is separate.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/31/20078/1/20078/1/2007PPASS
DetailsForrest France
Final shell fire sprinkler permit inspection passed, noted defficiencies corrected.
INSP-Final Inspection7/30/20077/31/20077/31/2007AFAIL
DetailsForrest France
Overspaced heads at locations on the 2nd and 3rd floors as indicated on site.
INSP-Final Inspection7/27/20077/30/20077/30/2007ADEFR
DetailsForrest France
To be completed in conjunction with the project related fire alarm permit final inspection.
INSP-Final Inspection7/25/20077/26/20077/26/2007AFAIL
DetailsForrest France
Low air switch at the dry system riser is not set properly, air compressor must be hard wired without an off switch, lacking coverage at one storage room in the basement, provide 911 signage at the outside bell, covered heads and missing escutcheons at some locations, head in the riser room is covered with fireproofing, inspection concluded at this time due to number of defficiencies.
INSP-Sprinkler Rough-in6/20/20076/21/20076/21/2007ACANC
DetailsForrest France
Wrong permit number called in for inspection.
INSP-Sprinkler Rough-in6/18/20076/19/20076/19/2007AFAIL
DetailsForrest France
Wrong permit number called in for inspection, was intended for a project related tenant improvement under FIR07-00270. Inspection failed due to overspaced heads at five locations, two heads in a conference room are cut in a the wrong ceiling height, missing approved plans which are required to be on site as a condition of the permit, a hold currently exists on this permit due to overdue fees.
INSP-Final Inspection6/1/20076/7/20076/7/2007ANR
DetailsForrest France
Per phone call from the contractor, project is not ready for final due to related alarm work issues.
INSP-Final Inspection5/9/20075/16/20075/14/2007ACANC
DetailsForrest France
Mike Bierman is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Sprinkler Rough-in/Hydro4/4/20074/5/20074/5/2007ADONE
DetailsForrest France
Air test concluded.
INSP-Supply line flush4/3/20074/4/20074/4/2007APART
DetailsForrest France
Air test restarted.
INSP-Sprinkler Rough-in3/21/20073/22/20073/23/2007AFAIL
DetailsForrest France
Dry system air test failed due to 3 psi. loss at the guage.
INSP-Sprinkler Rough-in3/20/20073/21/20073/21/2007APART
DetailsTroy Cobbley
This is a 24 hour air test. Test started at 11:00am with 40psi on the guage.
INSP-Sprinkler Rough-in1/31/20072/1/20072/1/2007AFAIL
DetailsForrest France
Per field inspection completed by B. Johnson, upright heads at several locations are obstructed by ductwork.
INSP-Supply line flush1/26/20071/29/20071/29/2007PPART
DetailsForrest France
UG supply line flush completed satisfactory, noted control valve manifold at the 2nd floor to be repiped for the provision of adequate and reasonable access.
INSP-Sprinkler Rough-in/Hydro12/6/200612/7/200612/7/2006APART
DetailsForrest France
UG hydrostatic test for the fire supply line completed satisfactory.
INSP-Sprinkler Rough-in11/16/200611/17/200611/17/2006APART
DetailsForrest France
UG fire supply line is acceptable for cover pending AG system design is compatible with the configuration of the underground supply piping.