Permit NumberFIR06-00733
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 12080 W MCMILLAN RD
Project NameSt Lukes Family Health Shell
Customer Number 
ePlanReview 
Description
St. Luke's Family Health (Medical Office Building Shell) - To construct a new 9,345 square foot, one story wood framed office shell building and related site improvements. This shell building will contain two future office tenant spaces. This is a shell permit only and no occupancy is allowed under this permit. Separate tenant improvement permits will be required to finish this building for occupancy. This permit is attached to BLD06-01466. The fire sprinkler scope of work includes installing a shell only, wet pipe system to serve the heated spaces and a dry pipe system to serve through out the attic space. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The Under Ground work was performed under a separate permit performed by others.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/12/20071/12/20071/12/2007PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection1/10/20071/11/20071/11/2007PCANC
DetailsTroy Cobbley
Per discussion with Troy this inspection will be rescheduled with the alarms and life safety
INSP-Sprinkler Rough-in/Hydro1/10/20071/11/20071/11/2007APASS
DetailsTroy Cobbley
24 hour air test on the dry system and the forward flush passed.
INSP-Sprinkler Rough-in/Hydro1/9/20071/10/20071/10/2007APART
DetailsTroy Cobbley
Overhead hydro test passed for the wet system. 24 hour air test started on the dry system at 8:30 with 40 3/4psi on the guage.
INSP-Sprinkler Rough-in/Hydro12/15/200612/18/200612/18/2006APART
DetailsTroy Cobbley
Wet system sprinkler piping is ok to cover except the three areas where the earthquaking still needs to be installed.
INSP-Sprinkler Rough-in/Hydro11/21/200611/21/200611/21/2006 PASS
DetailsTroy Cobbley
Underground hydro test passed.
INSP-Sprinkler Rough-in/Hydro10/13/200610/13/200610/13/2006APASS
DetailsTroy Cobbley
Dry system sprinkler piping ok to cover. I went over the requirement for resubmitting the fdc location with troy.