Permit Information
Permit NumberFIR06-00743
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 6941 S SUPPLY WAY
Project NameABC Supply - TI
Customer Number 
ePlanReview 
Description
(ABC SUPPLY) / RCE-6142 / To remodel an existing 19,000 sq ft office warehouse building for a new tenant per approved plans. Work to include, construction of new partitions to expand the existing office area from 990 sq ft to 1,957 sq ft within the warehouse for a showroom, installation of new suspended cieling system with related lighting, enclosing the exsiting riser room, Miscellaneous related interior finishes. This building is fully fire sprinklered any alterations to the sprinkler system shall be per NFPA #13 as regulated by the fire department. SEPARATE PERMITS REQUIRED FOR ANY RACKING OVER EIGHT FEET HIGH. *Rmh* Shiloh Fire Protection to install 10 new SSP's to accomondate new cielings in added showroom and riser room.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/13/200611/14/200611/14/2006APASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Sprinkler Rough-in10/24/200610/24/200610/24/2006PPART
DetailsTroy Cobbley
I gave the sprinkler contractor permission to cover the sprinkler piping but there are several outstanding issues still. No approved plans were on site so I could not verify if the corrected head spacing was alright. Also 8.0 K factor heads have been installed. I requested verification that the existing sprinkler system could support these heads. The fitter stated that Randy Knutson had already done this investigating. The annual inspection tag has not been updated at the riser.
INSP-Final Inspection10/13/200610/13/200610/13/2006PCANC
DetailsForrest France
Can we get this late in the day. Richard is the contact ####-####. Thanks; Phone #: ###-#### Internet Inspection Request from: Trent Bice Inspection cancelled from web by: Trent Bice
INSP-Final Inspection10/11/200610/12/200610/12/2006AFAIL
DetailsForrest France
Pendent sprinkler heads in the showroom area are mixed response and k factor, some heads are overspaced, need to provide a current annual inspection for the existing riser prior to final.