Permit NumberFIR06-00750
StatusFinaled
Name PROTEX
Site Address 6299 N EAGLE RD
Project NameSTAPLES
Customer Number 
ePlanReview 
Description
Fire Alarm System permit is to install a new fire alarm system for fire sprinkler and HVAC duct smoke detector monitoring. Fire alarm plans indicate audible visual notification installed throughout. Building Permit BLD06-01554 is to construct a new 20,000 square foot, one story office supply retail store and related site improvements. This building is constructed of masonry exterior wall with steel structural frame and roof joists with metal roof deck. All construction shall be per the approved plans and attached comment list. Grading & site utilities performed under BLD06-01979. No storage racks over 8 ft. in height allowed under this permit. JCM

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/13/200612/14/200612/14/2006APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection12/12/200612/13/200612/13/2006AFAIL
DetailsTroy Cobbley
Shut down of the hvac units by the duct smoke detectors did not function. It appears it might be a controls problem.Need to verify signals, install the foam filters on the sample tubes and remove the plastic short sample tubes since the steel one have been provided. All other fire alarm items are ok.
INSP-Final Inspection12/11/200612/12/200612/12/2006PFAIL
DetailsTroy Cobbley
No test performed since a supervisory signal from an unknown source was showing. The electricians where working on it as I left. No inspection performed.