Permit NumberFIR06-00811
StatusFinaled
Name RFI
Site Address 5850 N FIVE MILE RD
Project NameBONAVENTURE PLACE
Customer Number 
ePlanReview 
Description
This is a new required fire alarm system in a new senior residential apartment complex and assisted living center. The fire alarm system includes common area and residential smoke detectors alarm notification interface with nurse call system fire smoke damper control. Sprinkler system and HVAC system monitoring, elevator recall and door hold open release. In-Duct smoke detectors are not installed in lieu of corridor smoke detection. This building is fully sprinklered for allowable area increase and requirements due to occupancy use group based on building stories & number of units. The Building permit Bld06-00579 is to construct a 57,480 sq. ft., three story, and 75 Unit (less than 800 sq. ft. per unit) assisted living community to include support facilities, for use by persons unable take action to provide self preservation in an emergency situation. This building is classified as Type IIA construction in accord with State of Idaho Facility Standards. Building elements listed in Table 601, 2003 IBC are to be non-combustible. A non-combustible framed 2-hour fire wall is to be constructed between the 'I2' occupancy and 'A2' occupancy. DRH05-00320 CUP05-00028 drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/1/200710/2/200710/2/2007APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection9/28/20079/28/200710/1/2007PFAIL
DetailsTroy Cobbley
See Ken's field notes on the city approved plans for the items tested.
INSP-Alarm Testing9/24/20079/24/20079/24/2007PFAIL
DetailsTroy Cobbley
The fire alarm panel, after testing between two to six room detectors will automatically silence the sounder bases. I do not know if the panel silences all building alarms. Also the data from one of the tenant rooms is being corrupted by the time it is received at the facp and is causing "wave form" errors at the facp. I spoke to the Pyrotronics technical support and they believe that the silencing problem could be a logic/programming issue. They need to view the program to tell. I stopped the inspection out of concerns that if it is a hardware issue all of the items tested would have to be retested when a new panel is installed. Just to make a note when the main fire alarm panel is reset it takes nearly 7 minutes to return to normal. It also takes around 15 seconds to activate the sounder bases in the rooms. I was told this is due to the size of the system and a slow processor in the fire alarm panel. I spoke to Sam Rogers about these concerns. This entry has been made under this permit only due to none access to the other permits because of their being in the "review status"
INSP-Alarm Testing9/18/20079/21/20079/21/2007ADONE
DetailsTroy Cobbley
See the city approved plans for locations tested by Ken.
INSP-Alarm Testing9/18/20079/20/20079/20/2007ACANC
DetailsTroy Cobbley
Overbooked with Micron plan review.
INSP-Alarm Testing9/18/20079/19/20079/19/2007ADONE
DetailsTroy Cobbley
Todays inspection was actually a conference with the fire alarm designer. Mike Timmerman and I went over the a/v and smoke detector deficiencies with him. Mike is allowing him to red line the resubmittals that are waiting in line at the city for review.
INSP-Alarm Testing9/17/20079/18/20079/18/2007ADONE
DetailsTroy Cobbley
No actual inspection was perform today do to multiple problems found.They include the fire alarm panel does not sound on second alarm. There are many over spaced detectors in lounge area. There are areas where smoke detectors and a/v's need to be added. In the dining areas the cieling mounts a/v'sare know mounted on the walls. The kithen area has same problems as well. The contractor needs to resubmit these changes.
INSP-Alarm Testing9/17/20079/17/20079/17/2007AFAIL
DetailsTroy Cobbley
The dialer was in trouble and would not clear. No test performed.
INSP-Alarm Testing9/13/20079/14/20079/14/2007ADONE
DetailsTroy Cobbley
See the city approved plans for devices tested in area D.
INSP-Alarm Testing9/13/20079/13/20079/13/2007ACANC
DetailsTroy Cobbley
Overbooked
INSP-Final Inspection8/31/20079/4/20079/4/2007ACANC
DetailsTroy Cobbley
No alarm inspection performed today. Just sprinklers were looked at.