Permit Information
Permit NumberFIR06-00813
StatusFinaled
Name RFI
Site Address 5850 N FIVE MILE RD
Project NameBONAVENTURE PLACE
Customer Number 
ePlanReview 
Description
This is a new required fire alarm system in a new senior residential apartment complex and assisted living center. The fire alarm system includes common area and residential smoke detectors alarm notification interface with nurse call system fire smoke damper control. Sprinkler system and HVAC system monitoring, elevator recall and door hold open release. In-Duct smoke detectors are not installed in lieu of corridor smoke detection. This building is fully sprinklered for allowable area increase & compliance with occupancy use group. To construct a 1-hour fire-resistive, three story, 69 unit (26 units > 800 sq. ft.), multi family residential facility, separated from adjacent 'A2' Dining/common use area by a 2-hour fire wall to allow review of this portion as a stand alone structure for area & construction type. All fire-resistive assemblies shall be as called out on plans. DRH05-00320 CUP05-00028 drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/1/200710/2/200710/2/2007APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection9/28/200710/1/200710/1/2007AFAIL
DetailsTroy Cobbley
See Ken's notes on the city approved plans for items tested and deficiencies found.
INSP-Alarm Testing9/12/20079/12/20079/13/2007PDONE
DetailsTroy Cobbley
The fire alarm panel manufacturer, phone lines and supervision of NAC 4 and NAC 5 were verified. The smoke detector in the facp room and down the corridor as marked on the plans were tested. I found that the smoke detector and audio/visual were both overspaced from the end of the corridor. Also a NAC panel has been added in the facp room. Plans need to be resubmitted showing the new NAC. The facp was in trouble due to missing monitor modules at the roof top units. I went over requirements with the owner, building contractor, electrical contractor and fire alarm contractor.
INSP-Final Inspection8/31/20079/4/20079/4/2007ACANC
DetailsTroy Cobbley
No alarm inspection performed today. Just sprinklers were looked at.
INSP-Conference8/29/20078/31/20078/31/2007ADONE
DetailsTroy Cobbley
The fire alarm contractor wanted to know the specifics of why I can't dedicate specific times to show up and spend doing their inspection.