INSP-Final Inspection | 11/21/2006 | 11/22/2006 | 11/22/2006 | A | PASS |
Troy Cobbley
|
|
|
Hood suppression system operated correctly
|
INSP-Final Inspection | 11/20/2006 | 11/21/2006 | 11/21/2006 | A | FAIL |
Troy Cobbley
|
|
|
The lightes under the west hood in the back kitchen area did not turn off when the hood was activated. Signage at the pull stations is still needed.
|
INSP-Final Inspection | 11/17/2006 | 11/20/2006 | 11/20/2006 | P | FAIL |
Troy Cobbley
|
|
|
Did not test the systems because not all of the lights were operating on the main hood so I could not verify electrical shutoff. Also both fryers do not meet the 4' rule of outer lip of hood to the cooking surface as stated in the IMC. Also need signs for the manual pull stations.
|