Permit NumberFIR06-00838
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 2793 E HARD ROCK DR
Project Name 
Customer Number 
ePlanReview 
Description
This house shall be fitted with an NFPA 13D system, modified to include a single row of dry sidewall sprinklers along all walls common to attached garage and the living space. The system shall also be equipped with an alarm initiating device commonly referred to as a flow switch, and an outside alarm indicating device. This permit is attached to: BLD06-00174.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/20/200712/20/200712/20/2007PPASS
DetailsForrest France
All corrections made per forest notes.KR
INSP-Final Inspection12/19/200712/20/200712/20/2007AFAIL
DetailsForrest France
Heads at three locations are blocked by ceiling mounted obstructions and do not meet criteria per 8.10.6.1.2 NFPA 13 2002. UG supply flush completed okay.
INSP-Final Inspection12/18/200712/19/200712/19/2007PFAIL
DetailsForrest France
No approved set of plans on site, will call this in for tomorrow to do under ground flush and final. KR
INSP-Final Inspection12/18/200712/19/200712/18/2007PCANC
DetailsForrest France
Reschedule final, Brian F is the contact. Thank you. Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Final Inspection12/17/200712/18/200712/18/2007PNR
DetailsForrest France
According to project history, the underground supply has not yet been witnessed for flushing as required. Per phone conversation, contractor is not prepared to complete flushing today and will reschedule for tomorrow.
INSP-Final Inspection2/9/20072/12/20072/12/2007PCANC
DetailsTroy Cobbley
To be rescheduled when the correct outlet for flushing has been installled. No inspection was performed.
INSP-Supply line flush2/9/20072/12/20072/12/2007PCANC
DetailsTroy Cobbley
To be rescheduled when the outlet for the underground flush has been installed.
INSP-Sprinkler Rough-in12/14/200612/15/200612/15/2006APART
DetailsForrest France
Corrections required for OH fire sprinkler cover are complete, rough-in installation is approved for cover.
INSP-Sprinkler Rough-in12/13/200612/13/200612/14/2006PFAIL
DetailsForrest France
Incorrect and missing tenting at one location, the maximum bending deflection distance exceeds the allowable amount at one room on the east side, approved plans must remain on site at all times per condition of the permit.