Permit Information
Permit NumberFIR06-00920
StatusFinaled
Name PROTEX
Site Address 4095 S GEKELER LN
Project NameAce Company
Customer Number 
ePlanReview 
Description
This fire alarm permit is to install a fire sprinkler monitoring panel in a new building. Building Permit # BLD06-01671 is to construct a new 9,600 square foot, one story, pre-engineered steel fabrication building and related site improvements. All construction shall be per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/24/20071/24/20071/24/2007APASS
DetailsForrest France
Corrections have been verified for completion, final alarm inspeciton passed.
INSP-Final Inspection1/23/20071/23/20071/23/2007PFAIL
DetailsTroy Cobbley
The fire alarm panel's display showed abunch of gibberish when testing phone line #2 and would not clear until all power had been dumped. Per Matt with Silent Knight technical support the panel should be replaced. The serial numbers on the existing panel mother bord are SN38273. These should change with a new board. Entire system will need to be tested.
INSP-Final Inspection1/22/20071/22/20071/22/2007PFAIL
DetailsForrest France
The PIV tamper switch is not correctly installed or adjusted, also lacking NFPA 72 record of inspeciton and testing to be completed (per review comments) prior scheduling final field acceptance test.