Permit Information
Permit NumberFIR06-00942
StatusFinaled
Name CRANE ALARM COMPANY
Site Address 3111 S BOWN WAY
Project NameBown Crossing Market Place
Customer Number 
ePlanReview 
Description
This permit is to Install a fire sprinkler and HVAC monitoring panel. System includes elevator recall functions and Per IFC review Cooking Hood monitoring is required. Building Permit # BLD06-02349 is to construct interior improvements for a new restaurant/bar tenant to be located within a new 6,696 square foot, 2 story building. Work is to include 3 restrooms accessible to the disabled, interior nonbearing walls, suspended ceilings, millwork, and finishes. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. CZC06-00152 **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/5/20072/7/20072/7/2007APASS
DetailsTroy Cobbley
permit finaled
INSP-Alarm Testing1/25/20071/29/20071/30/2007PFAIL
DetailsForrest France
SD at the elevator lobby failed to recall the car, need to test the hood suppression system interconnection, provide access for testing of the PIV tamper, noted one duct detector in need of revision of sample and vent tube orientation (repaired while on site), remove the duct insulation liner at the vent tube on the remaining duct detectors. The panel, manual pull, SD at panel, waterflow and sprinkler main control tested okay. Also need verification of signals recieved as discussed.