Permit NumberFIR06-00945
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 3901 W HILLCREST DR
Project Name 
Customer Number 
ePlanReview 
Description
To install a life safety NFPA 13D system in an existing new eight bedroom, three bath, one story single family dwelling. In order to meet requirements, the system will include a 400 gal. holding tank and a 5hp booster pump as adequate supply and pressure was not available through the public water supply.
System shall be equipped with an alarm initiating device and an outside alarm. All fire sprinkler work and related, which includes dual use, single service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/2/20072/5/20072/5/2007PPASS
DetailsForrest France
Fire sprinkler passed final field inspection, contractor to provide missing "911"sign at the outside bell as discussed.
INSP-Final Inspection2/1/20072/2/20072/2/2007PDEFR
DetailsForrest France
Inspection to be completed in conjunction with the FA permit on 2/5 as scheduled.
INSP-Sprinkler Rough-in/Hydro1/31/20072/1/20072/1/2007PPART
DetailsForrest France
Per field inspection by B. Johnson, the overhead fire sprinkler rough-in including the booster pump and holding tank are acceptable.