Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR06-00995
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 1375 W PARKHILL DR
Project Name 
Customer Number 
ePlanReview 
Description
To install a (modified) life safety NFPA 13D in a 3,295-f/2 two story single family dwelling with an attached three car garage. The modification is the installation of a single row of dry sidewall sprinklers along the common wall attached to the garage and the living space. System shall be equipped with an alarm initiating device and an outside alarm. All fire sprinkler work and related, which includes dual use, single service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD06-02400.
A Re-Submittal Is Required On The Following
1. Add a line of dry sidewall heads along the common wall in the garage which separates the garage from the living space. If the demand of these heads exceeds that of the remote area submitted than a complete set of calculations shall also be required.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/19/20079/20/20079/20/2007APASS
DetailsForrest France
Final inspection passed, supply line flushed, double check backflow to be certified today, one missing escutcheon installed and travel cap at the ssu at the riser removed while on site, also need to install a test orifice at the inspectors test connection.
INSP-Final Inspection9/19/20079/19/20079/19/2007PCANC
DetailsForrest France
mike Phone #: ###-#### rescheduled for tomarrow morning
INSP-Sprinkler Rough-in1/25/20071/26/20071/26/2007PPART
DetailsForrest France
Overhead fire sprinkler install is approved for cover.
INSP-Sprinkler Rough-in1/17/20071/18/20071/18/2007APART
DetailsForrest France
OH rough-in inspection is acceptable pending the addition of a head at the riser within 1' of the exposed CPVC, missing batt insulation at two 1" riser pc. locations, the second floor loft/bedroom above the garage lacks piping cold cavity protection at this time.