Permit Information
Permit NumberFIR07-00125
StatusFinaled
Name FIREXPERT
Site Address 905 W ROYAL BLVD
Project NameParks Royal Body Works - Paint
Customer Number 
ePlanReview 
Description
The installation of a pre manufactured paint booth with fixed fire suppression sytem.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/21/20072/22/20072/22/2007PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection2/19/20072/20/20072/21/2007AFAIL
DetailsTroy Cobbley
Booth suppression system activated when the test link was cut. The air supply for painting shut off as well. The booth does not have the 3' clearance as required but seems to meet the exception for being against a non combustible wall. The wall is cinderblock which supports a sheetrock ceiling. The item that is a problem is the heater for the curing/baking process is direct fire which is not allowed per code. Also the distance from property lines and openings needs verified as well as the height of the exhaust discharge piping. Matt was going to have his booth supplier contact sam rogers about their booth and its operation. Also I had matt program in the required 3 minute delay before the heater comes on per code and per matt the unit has a high limit switch set at 200 degrees. The fire extinguisher is also ok.
INSP-Final Inspection2/15/20072/16/20072/16/2007PCANC
DetailsTroy Cobbley
Per contractor piping needs to be rerouted around electrical cabinet. No inspection was performed.