Permit Information
Permit NumberFIR07-00129
StatusFinaled
Name LEA ELECTRIC LLC
Site Address 1112 W MAIN ST
Project NameROYAL PLAZA
Customer Number 
ePlanReview 
Description
This permit is to install a high-rise fire alarm system in a new shell and core building. This permit does not allow occupancy. The building fire alarm system includes, but not limited to a required manual and automatic fire alarm system to include Initiating and Notification Appliances in core areas of the building. Fire command center, Voice evacuation, Fire fighter communications (phones), Fire sprinkler and fire pump monitoring, HVAC Duct smoke detectors, In-duct smoke detection, Fire smoke dampers, Elevator recall, Shunt Trip and Offsite Reporting. Building Permit # BLD06-00450 is to build a new 97,585 square foot, seven story mix occupancy high rise shell and core building and related site improvements. This building is constructed of geopier and concrete foundation, steel structural frame and concrete floors. This building is fully fire sprinklered. The first floor will have retail, restaurant and parking (8 spaces) and building electrical and mechanical support areas. The second floor is parking (30 spaces). The third through sixth floor will be residential condominium units. The seventh floor will be individual residential storage units (26 units) an exercise room and a 1300 square foot roof top trellis covered terrace. This is a shell permit only and no occupancy is allowed under this permit. Separate tenant improvement permits will be required to finish this building for occupancy. All construction shall be per the approved plans and attached comment list. Note: Grading/geopier permit issued under MIS06-00064. Partial foundation & stair towers issued under BLD06-01349. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/6/200712/6/200712/6/2007PPASS
DetailsForrest France
Shell and core fire alarm permit passed final inspection, as-built documentation to be delivered as discussed.
INSP-Final Inspection12/5/200712/5/200712/5/2007AFAIL
DetailsForrest France
Need correction notice items one and two completed prior to final acceptance, also noted SD covers at three locations.
INSP-Final Inspection12/4/200712/4/200712/4/2007PFAIL
DetailsForrest France
See correction notice left on site for a list of items needed for permit final.
INSP-Final Inspection11/29/200711/29/200711/29/2007PPART
DetailsForrest France
Fire alarm passed. Cannot final, pending core and shell final.KR
INSP-Final Inspection11/28/200711/28/200711/28/2007PDEFR
DetailsForrest France
See inspection comments per M. Timmerman.
INSP-Final Inspection11/27/200711/27/200711/27/2007PCANC
DetailsForrest France
Overbooked.
INSP-Alarm Testing11/23/200711/23/200711/23/2007PPART
DetailsForrest France
Inspection activity completed 11/21 including shell and core alarm work for the 4th thru 6th and penthouse testing, also tested sprinkler monitoring for the floor control valves, noted some items in need of correction including programming for the DH release at the trash chute doors, as-built address changes, and field mods.
INSP-Alarm Testing11/19/200711/20/200711/20/2007APART
DetailsForrest France
Begin fire alarm testing today including all related elevator control devices, FACP, batteries, phone lines, smoke at panel,FJ and initiation and detection devices for the 1st thru 3rd floors not including sprinkler monitoring tested today. Noted some device address changes, three deleted ID detectors, one pull station at the NW exit is still too high, need to provide a clean set of as-builts for field modifications and a current map at the panel.