Permit Information
Permit NumberFIR07-00134
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 4719 S MARKET ST Unit: 103
Project NameAssociated Foods Warehouse
Customer Number 
ePlanReview 
Description
ASSOCIATED FOODS WAREHOUSE - SE CORNER TENANT SPACE 103) Create a 33,602 sq.ft. secure tenant space within an existing 250,000 sq ft building for storage of high pile insulation product, per approved plans. Work to include, erection of 18 ft high metal and gyp-board partitions, construction of a new vestibule, installation of new exterior overhead door located on the south side of the building,
The fire sprinkler scope of work includes the demo of the existing electric fire pipe as it will be replaced with a new diesel fire pump rated 2500 gpm @ 110 psi. The existing 2 ½” branch lines will also be remove and replaced with 3” branch lines. The existing heads with in the affected areas will also be removed and replaced with ESFR heads. In addition four existing rack system supply risers and associated piping will be removed as per plan. This building is fully fire sprinkled any alterations or modifications to the sprinkler system shall be per NFPA #13 as regulated by the fire department. The partition walls separate the areas into spaces that are less than 50,000 sq ft so that smoke and heat vents are not required. Fire sprinkler work is related to selective demolition, construction of new non-combustible interior partitions, & the installation of new suspended ceiling system per plans, attached plan review conditions, regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD06-02402.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/7/200711/8/200711/8/2007APASS
DetailsForrest France
Corrections are complete, fire sprinkler permit finaled.
INSP-Final Inspection9/21/20079/24/20079/25/2007APART
DetailsForrest France
Overhead rough-in is complete, noted six items in need of correction- see inspection comments for related sprinkler permit FIR07-00106.
INSP-Final Inspection9/19/20079/21/20079/21/2007APART
DetailsForrest France
OH hydrostatic testing completed satisfactory.
FIR-Aging Inspection8/13/20078/13/20078/14/2007 PART
DetailsForrest France
Work in progress.