Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR07-00141
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1112 W MAIN ST Unit: 505
Project NameROYAL PLAZA
Customer Number 
ePlanReview 
Description
This TI in suite #505 includes dropping 27 residential heads into the new wall and ceiling layout of the dwelling unit and 3 other Dry SSP heads on the terrace. The work shall be performed in accordance with NFPA13R installation guidelines. This building is fully fire sprinklered for one-hour substitution. The fire sprinkler system work shall comply with IFC 2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD6-03522.
When tenant work affects fire sprinkler protection outside the permitted work area due to the installation of tenant-demising or new partition walls, the affected area sprinkler coverage outside the BLD permit will fall under the Fire Permit scope of work, to maintain the required fire protection within the fire sprinklered facility. The “Riser” and its supplies which include all appurtenances (including tamper, alarm and alarm monitoring) relating to the normal and correct function and integrity of this system will fall under the jurisdiction for code compliant verification.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/13/20082/15/20082/15/2008APASS
DetailsForrest France
Painted escutcheons at two locations replaced while on site, as-built plans accepted, permit finaled.
INSP-Sprinkler Rough-in/Hydro10/25/200710/26/200710/29/2007PPART
DetailsForrest France
Hydro test passed.
INSP-Final Inspection8/22/20078/23/20078/23/2007APART
DetailsForrest France
Overhead rough in is good for cover at the hard lid ceiling areas, changes to floor plan are noted.
INSP-Sprinkler Rough-in8/16/20078/17/20078/17/2007ANR
DetailsForrest France
Pending light fixture obstruction issues.