INSP-Final Inspection | 11/28/2007 | 11/28/2007 | 11/28/2007 | P | PASS |
Forrest France
|
|
|
Corrections verified for completion, fire sprinkler permit finaled.
|
INSP-Final Inspection | 11/26/2007 | 11/27/2007 | 11/28/2007 | P | PART |
Forrest France
|
|
|
Reinspection for the cleanroom area defficiencies passed, also inspected first floor and mech. penthouse added and relocated heads due coverage issues.
|
INSP-Final Inspection | 11/13/2007 | 11/14/2007 | 11/15/2007 | A | FAIL |
Forrest France
|
|
|
Noted several locations where heads are overspaced, blocked, or installed beyond listed spacing and max. allowable area.
|
INSP-Final Inspection | 11/12/2007 | 11/13/2007 | 11/13/2007 | P | CANC |
Forrest France
|
|
|
Mike B is the contact, thank you. Phone #: ###-#### Internet Inspection Request from: Stan Beus
|
INSP-Final Inspection | 11/8/2007 | 11/9/2007 | 11/9/2007 | A | CANC |
Forrest France
|
|
|
Mike B is the contact, thank you. Phone #: ###-#### Internet Inspection Request from: Stan Beus
|
INSP-Final Inspection | 8/30/2007 | 8/31/2007 | 8/31/2007 | P | NR |
Forrest France
|
|
|
Missing as-built plans for verification of field mods.
|
INSP-Sprinkler Rough-in | 8/30/2007 | 8/31/2007 | 8/30/2007 | P | CANC |
Forrest France
|
|
|
Please call 1/2hr prior to inspection. Mike B is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
|
INSP-Final Inspection | 8/23/2007 | 8/27/2007 | 8/27/2007 | A | PART |
Forrest France
|
|
|
Project is not ready for final per contractor due to missing ceilings at several locations, need to complete final walk-through with provided as-built plans reflecting field modifications.
|
INSP-Sprinkler Rough-in | 7/16/2007 | 7/16/2007 | 7/16/2007 | A | PART |
Forrest France
|
|
|
See approved plan set for defficient areas.
|
INSP-Sprinkler Rough-in/Hydro | 7/12/2007 | 7/13/2007 | 7/13/2007 | A | PART |
Forrest France
|
|
|
OH hydrostatic testing completed acceptable, rough-in reinspect for the fan deck area failed due to missing hanger at added arm-over to a head beneath a duct at the NW corridor, also installed incorrect size rings at added branch line hangers in the fan attic 201D, stair #4 200Y is not complete at this time.
|
INSP-Sprinkler Rough-in | 7/5/2007 | 7/9/2007 | 7/9/2007 | P | FAIL |
Forrest France
|
|
|
Reinspected defficient items on sheet FP8-completed okay. See sheet FP9 and 10 on approved plans for 3rd floor fan deck inspected today, red lined areas in need of correction including hangers, lacking coverage, seismic clearance at the riser main, blocked heads, retaining straps, etc.
|
INSP-Sprinkler Rough-in | 6/25/2007 | 6/26/2007 | 6/26/2007 | P | FAIL |
Forrest France
|
|
|
Inspected OH rough-in for the 2nd level areas A and B sheets FP5 and 6, noted on plans defficient areas with missing heads, overspaced heads, hangers, retaining straps, areas not yet complete etc., flex heads in the cleanroom are not completed at this time.
|
INSP-Sprinkler Rough-in | 6/21/2007 | 6/22/2007 | 6/22/2007 | P | FAIL |
Forrest France
|
|
|
Completed rough-in inspection for the basement subfab, process bay and chem. labs per sheet FP3, noted locations where head spacing, seismic bracing, and hangers need to be corrected, circled areas where install is not complete.
|