INSP-Final Inspection | 5/4/2007 | 5/7/2007 | 5/7/2007 | A | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Final Inspection | 3/21/2007 | 3/26/2007 | 3/26/2007 | P | PART |
Forrest France
|
|
|
Corrections from previous inspection have been finished, need to install drop ceiling and escutcheons prior to final.
|
INSP-Sprinkler Rough-in/Hydro | 3/15/2007 | 3/16/2007 | 3/16/2007 | A | FAIL |
Forrest France
|
|
|
Static pressures above 100 psi. require hangers within 1' of the end on armovers supplying pendent sprinklers at the ATM lobby.
|