Permit Information
Permit NumberFIR07-00213
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 10823 W FRANKLIN RD
Project NameSantara Place Condominiums
Customer Number 
ePlanReview 
Description
* To install a fire life safety NFPA 13R system to prevent flashover (total involvement) in the room of fire origin, where sprinklered, and to improve the chance for occupants to escape or be evacuated, in a new 8,191-ft/2 two story, ten unit apartment building starting at the top of a 2” Watts Series 007 Backflow Double Check control. All fire sprinkler work and related, which includes dedicated 2” underground water supply and the backflow prevention device shall be per NFPA 13R, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD06-01170.Revised Scope of Work 02/06/08
These previously approved plans were resubmitted as an as-built set dated 02/06/2008 and noted as revision reference #1. The modification did affect the 4 remote areas of hydraulic calculations. The calculations have also been submitted for review but do not appear to adversely affect the operation of the system as it was approved.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/6/20088/8/20088/8/2008PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection8/5/20088/6/20088/6/2008PCANC
DetailsTroy Cobbley
Per Jim Danes the replacement sprinkler canopies are on order. The inspection will be called in at a later time.
INSP-Final Inspection8/5/20088/5/20088/5/2008PFAIL
DetailsTroy Cobbley
Need verification that the canopies have been factory painted. All other items are ok.
INSP-Final Inspection8/4/20088/5/20088/5/2008AFAIL
DetailsTroy Cobbley
Need verification that the canopies have been factory painted. All other items are ok.
INSP-Sprinkler Rough-in/Hydro6/19/20086/20/20086/20/2008APASS
DetailsTroy Cobbley
Above ground hydro test passed.
INSP-Sprinkler Rough-in/Hydro5/21/20085/22/20085/22/2008PPASS
DetailsTroy Cobbley
Underground hydro test passed
INSP-Sprinkler Rough-in4/30/20085/1/20085/1/2008APASS
DetailsTroy Cobbley
Permit finaled. Simplex to provide as-builts.
INSP-Sprinkler Rough-in2/15/20082/19/20082/19/2008APASS
DetailsTroy Cobbley
The underground supply piping for building "A" is ok for cover
INSP-Sprinkler Rough-in/Hydro2/5/20082/6/20082/6/2008APASS
DetailsTroy Cobbley
The sprinkler piping is ok to cover. Contractor provided Brian Johnson revised hydraulic calculations. The fire sprinkler contractor still needs to provide resubmittals for all of the changes that have occured prior to a final inspection for this project.